125
Section V.
Parameter Function Table
A6.24
AI1 set hopping point
-100.0%~100.0%
0.0%
☆
A6.25
AI1 set hopping amplitude
0.0%~100.0%
0.5%
☆
A6.26
AI2 set hopping point
-100.0%~100.0%
0.0%
☆
A6.27
AI2 set hopping amplitude
0.0%~100.0%
0.5%
☆
A6.28
AI3 set hopping point
-100.0%~100.0%
0.0%
☆
A6.29
AI3 set hopping amplitude
0.0%~100.0%
0.5%
☆
Analog input AI1~AI3 of HV590 are all provided with hopping function for set value.
Hopping frequency refers to fixing of analog corresponding setup to the value of hopping point
when analog correspondending setting varies within jump point upper/lower limit.
E.g
:
Voltage of analog input AI1 is in 5.00V fluctuation, which range is 4.90V~5.10V. Minimum input
0.00V corresponding to 0.0%, while maximum input 10.00V corresponding to 100.%.The corresponding
setting of AI1 fluctuates between 49.0%~51.0%.
Set A5.16 to 50.0% and A5.17 to 1.0%, after hopping function processing, AI1 is fixed as 50.0%. In
this way, AI1 is converted into a stable input, and fluctuation is eliminated.
5.23
User programmable card parameters
:
A7.00-A7.09
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
A7.00
User programmable function
selection
Invalid
0
0
★
Valid
1
A7.01
Control board output terminal
control mode selection
Inverter control
0
-
★
User programmable card control
1
1bit
Y1P(Y1 as pulse output)
10bit
Relay(T/A1-T/B1-T/C1)
100
bit
DO1
1000
bit
Y1R(Y1 as switch output)
10000
bit
AO1
A7.02
Programmable card expansion
AI3x function configuration
See
《
User programmable control card
》
for
supplementary description
-
★
A7.03
Y1P output
0.0%-100.0%
0.0%
☆
A7.04
AO1 output
0.0%-100.0%
0.0%
☆
A7.05
Switch output
1bit
Y1R
000
☆
10bit
Relay 1
100
bit
DO
A7.06
Programmable card
frequency setup
0.0%-100.0%
0.0%
☆
Содержание HV590 Series