HV350 Mini Frequency Inverter User Manual
92
PA.17
Delay time of sleeping
Setting range
:
0.0
~
3600S
PA.18
Sleeping frequency
Setting range
:
0.0
~
400.0Hz
PA.19
Delay time of waking
Setting range
:
0.0
~
60S
PA.20
Waking value
Setting range
:
0.0
~
100%
实际值
For PID control, parameters PA.17~ PA.20 define delay time of sleeping,
sleeping frequency, delay time of waking and waking value.
t<td
td
PID input
( PA. 20)
( PA. 19)
td=
PA. 17
( PA. 18)
PID
Actual value
Delay time of waking
Delay time of sleeping
Sleeping frequency
(Output frequency)
stop
run
time
Fig. 6-30 PID sleeping and waking
Pb Traverse function
Pb.00
Traverse mode
Setting range
:
0
、
1
0:
Auto mode
At first, the drive operates at preset frequency of traverse operation (Pb.01)
for certain time (Pb.02), and then enter traverse mode automatically.
1:
Manual mode
If the multi-function terminal (Xi is set to terminal function 20) is enabled,
the drive will enter traverse mode. If the terminal is disabled, the drive
will exit traverse operation and operate at the preset traverse frequency
(Pb.01).