For example, connect AO1 with a voltage meter (range: 0~5V) to indicate
operating frequency, and the range of operating frequency is 0~50Hz (Maximum
frequency=50Hz), then F8.00=0(=frequency), F8.02=0(=0V), F8.03=0(0Hz),
F8.04=50%(=5V), F8.05=100%(=50Hz).
0
AO1 Output signal
output(F8.00)
Minimum value
(F8.02)
Corresponding to the
minimum value
(F8.03)
Maximum value
(F8.04)
Corresponding to the
maximum
(F8.05)
Fig. 6-28 Relationship between maximum/minimum AO1 and F8.00
P9 Program operating parameters
P9 parameter group is function code of programming operation.
Both programming operation and multi-frequency operation are used for
realizing the inverter's variable speed running according to certain regulations.
One cycle of programming operation is shown in Fig. 6-29, f1
~
f7 and T1
~
T7 will be defined in the following function codes.