background image

Intesis

TM

 INMBSMID---I000

 

     

User’s Manual r

1.3 EN

 

 

  

 

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                15 / 24

 

4.4

 

Considerations on Temperature Registers 

 
The next information refers to INMBSMID001I000 and may not apply to INMBSMID004I000 
/ INMBSMID008I000 /INMBSMID032I000. 
 

 

AC unit temperature setpoint (R/W)

  

(register 4 

 in Protocol address / register 5 

 in PLC address): 

This is the adjustable temperature setpoint value required by the user.  
 
This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 
16). If present, a remote controller

 

connected to the Midea indoor unit will report the 

same temperature setpoint value as this register,  but only will happen when no AC 
unit´s external reference is provided from INMBSMID001I000 (see detail for register 
22/23 below). 
 

 

AC unit temperature reference (R)

  

(register 5 

 in Protocol address / register 6 

 in PLC address): 

This register reports the temperature that is currently used by the Midea indoor unit 
as the reference of its own control loop. Depending on the configuration of the indoor 
unit, this value can be the temperature reported by the sensor on the return path of 
the Midea indoor unit or the sensor of its remote controller. It is a read-only register 
(Modbus functions 3 or 4). 

 

 

AC unit external temperature reference (Modbus) (R/W)

  

(register 22 

 in Protocol address / register 23 

 in PLC address):  

This  register  allows  to  provide  an  external  temperature’s 

value  from  the  Modbus 

side. The Midea indoor unit does not allow to provide an external temperature to be 
used as a reference of the control loop of the AC indoor unit. In order to overcome 
this  limitation  and  enable  the  usage  of  an  external  temperature  sensor  (i.e.  from 
Modbus side), INMBSMID001I000 

applies the following mechanism (only if “external 

temperature’s reference” is bein

g used): 

 

o

 

After  a  couple  of  values  have  been  entered  in  the  “AC  unit  external 

temperature’s reference” (register 22/23) and “AC unit temperature set point” 

(register  4/5),  INMBSMID001I000  is  going  to  estimate  the  chosen 
temperature  differences 

(e.g.  if  a  “temperature  setpoint  (register  4/5)”  of 

22ºC

, and an “external temperature reference (register 22/23)” of 

20ºC 

are 

entered, INMBSMID001I000 will assume that the user is demanding a 

+2ºC

 

increase in temperature). 
 

o

 

By knowing at any time the ambient temperature currently used by the indoor 

unit  to  control  its  own  operation  (register  5/6),  INMBSMID001I000  can 
calculate  the  required  temperature  setpoint  needed  to  apply  the 
decrease/increase on the real temperature and reach the temperature chosen 
by  the  user  (following  the  example  above,  if  INMBSMID001I000  reads  an 

“ambient temperature” (register 5/6) of 

24ºC

 in the indoor unit, it will apply 

a final setpoint of 

24ºC + 2ºC = 26ºC

). 

 

o

 

At  this  moment,  each  time  that  INMBSMID001I000  detects  a  change  on  the 

ambient  temperature  reported  by  the  indoor  unit  (register  5/6),  it  will  also 
change  the  required  setpoint,  in  order  to  keep  the  temperature  required  by 
the  user  at  any  time.  If  we  follow  the  last  example,  if  INMBSMID001I000 
receives  a  new  temperature´s  value  coming  from  the  indoor  unit  of 

25ºC

INMBSMID001I000  will  automatically  adjust  the  temperature  setpoint 
required of the AC indoor unit to 

25ºC + 2ºC = 27ºC

). 

 

Содержание Intesis INMBSMID I000 Series

Страница 1: ...Compatible with VRF and Commercial lines USER MANUAL Issue date 05 2018 r1 3 ENGLISH...

Страница 2: ...ion is subject to change without notice URL https www intesis com 2 24 Modbus RTU EIA 485 Interface for Midea air conditioners Compatible with VRF and Commercial lines ORDER CODE LEGACY ORDER CODE INM...

Страница 3: ...d are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables a...

Страница 4: ...er 9 4 2 Modbus Registers for INMBSMID001I000 9 4 2 1 Control and status registers 9 4 2 2 Configuration Registers 11 4 3 Modbus Registers for INMBSMID004I000 INMBSMID008I000 INMBSMID032I00012 4 3 1 G...

Страница 5: ...NMBSMID008I000 INMBSMID032I000 devices can be connected on the same network INMBSMID I000 is a Modbus slave device Direct connection to the Midea XYE bus Configuration from both on board DIP switches...

Страница 6: ...r of AC units to control the recommended connection methods can be seen in Figure 2 1 and Figure 2 2 NOTE If a CCM Central Controller is present in the XYE bus then the INMBSMID I000 cannot be connect...

Страница 7: ...connected Please disconnect the CCM Central Controller for use of the gateway 90 mm 3 5 MODBUS RTU EIA 485 Bus EIA485 A B X Y V1 V2 AC Unit Power 53 mm 2 1 For wall mounting extract the upper and dow...

Страница 8: ...nnect the Modbus RTU EIA 485 bus to the EIA485 A B connector of the interface 5 Connect the power cable between the interface and the Mains Power following the instructions of the diagram Screw each b...

Страница 9: ...needs to be set in the AC unit 4 2 1 Control and status registers Register Address protocol address Register Address PLC address R W Description 0 1 R W AC unit On Off 0 Off 1 On 1 2 R W AC unit Mode...

Страница 10: ...ambient temperature from external sensor at Modbus side 1 2 3 7 32768 Initialization value No temperature is being provided from an external sensor Any other C x10 C F 23 24 R AC Real temperature set...

Страница 11: ...minutes 14 15 R Modbus RTU Baud rate 2400bps 4800bps 9600bps Default Value 19200bps 38400bps 57600bps 76800bps 115200bps 15 16 R Device s Modbus Slave address 1 63 21 22 R Max number of fan speeds 49...

Страница 12: ...the interface Register Address protocol address Register Address PLC address R W Description 0 1 W AC unit On Off Global 0 Off 1 On 1 2 W AC unit Mode Global 12 0 Auto 1 Heat 2 Dry 3 Fan 4 Cool 2 3 W...

Страница 13: ...78 Initialization value 17 30 C C x10 C 63 86 F 1000 20 n 5 1000 20 n 6 R AC unit Temperature reference 16 17 18 32678 Initialization value Ranges determined by the Manufacturer of the AC indoor unit...

Страница 14: ...200 2031 2032 R Capacity 22 4 INMBSMID004I000 4 Indoor Units 8 INMBSMID008I000 8 Indoor Units 32 INMBSMID0032I000 32 Indoor Units 2040 2041 R Modbus RTU Baud rate 2400bps 4800bps 9600bps Default 19200...

Страница 15: ...unit does not allow to provide an external temperature to be used as a reference of the control loop of the AC indoor unit In order to overcome this limitation and enable the usage of an external tem...

Страница 16: ...pplied The temperature setpoint s value shown by the Remote Controller from Midea connected to the indoor unit shall show a different value from the value shown in register 4 5 Instead it shall show t...

Страница 17: ...1 AC indoor unit s features SW1 P1 4 Description AC Unit does not have AUTO mode Default value AC Unit has AUTO mode AC Unit does not have DRY mode Default value AC Unit has DRY mode AC Unit does not...

Страница 18: ...e magnitude C F and EIA 485 termination resistor Table 4 3 SW4 Temperature and termination resistor configuration SW4 P1 2 4 Description Temperature values in Modbus register are represented in degree...

Страница 19: ...Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 20: ...ce LED indicator The device includes LED indicators to show all the possible operational states In the following table you will find the possible indication combinations and its meaning L1 green LED D...

Страница 21: ...h are listening the bus when all the transmitters outputs are in three state high impedance a fail safe biasing mechanism is required This mechanism provides a safe status a correct voltage level in t...

Страница 22: ...d or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x Serial EIA485 Plug in screw terminal block 2 poles A B Compat...

Страница 23: ...ormation is subject to change without notice URL https www intesis com 23 24 6 List of supported AC Unit Types A list of Midea indoor unit model s references compatible with INMBSMID I000 and its avai...

Страница 24: ...ter module protection 13 EC Cooling error 14 ED Outdoor unit fault protection 15 EE Water level fault detection 16 EF Other errors 101 P0 Vaporizer temperature protection 102 P1 Thawing or cold air pr...

Отзывы: