General Fieldbus Parameters
Index range 3000h - 300Fh is allocated for general fieldbus parameters. The valid data range may
differ depending on the slave interface.
Index
Subindex
Type
Access
Name and Description
Comment
3000h
128
U16
RW
Input Data Size (to primary network)
Valid values: 2-512, default 16
3001h
0
U16
RW
Output Data Size (from primary network)
Valid values: 2-512, default 16
Writing to object 1010h will verify the stored Input/Output Data sizes against the current
fieldbus limitations. If the data sizes do not comply, error code 6600h will be generated.
The gateway must be restarted for changes to take effect on the primary network.
7.3.5
Primary Network Specific Parameters
Index range 3010h - 30AFh is allocated for parameters that are specific for the different primary
networks available in the Anybus X-gateway CANopen model range.
Index
Subindex
Type
Access
Name and Description
Comment
PROFIBUS specific parameters:
3011h -
301Fh
-
-
-
(reserved for future use)
CANopen primary network specific parameters:
3020h
0
U8
RW
CANopen Offline Option
Specifies which event will cause the module
to report the bus as offline.
Valid values:
1 (bus error)
2 (node guarding or heartbeat)
3021h -
302Fh
-
-
-
(reserved for future use)
DeviceNet specific parameters:
3031h -
303Fh
-
-
-
(reserved for future use)
Modbus RTU specific parameters:
3040h
0
U16
RW
Offline timeout
Valid values: 0–65535
3041h -
304Fh
-
-
-
(reserved for future use)
ControlNet specific parameters:
3051h -
305Fh
-
-
-
(reserved for future use)
Modbus TCP specific parameters:
3060h
0
U16
RW
Offline timeout
Valid values: 0–65535
Communication in Modbus-TCP is handled with a query/response protocol. The offline timeout parameter defines the time limit for how
longe the slave/adapter will go offline. If the parameter is set to zero, the functionality is disabled.
3061h -
306Fh
-
-
-
(reserved for future use)
EtherNet/IP specific parameters:
3071h -
307Fh
-
-
-
(reserved for future use)
PROFINET IO specific parameters:
3081h -
308Fh
-
-
-
(reserved for future use)
EtherCAT specific parameters:
3091h -
309Fh
-
-
-
(reserved for future use)
Anybus
®
X-gateway
™
CANopen
®
PROFINET
®
IRT (2.32) User Manual
SCM-1202-029 1.2 en-US