AB7609 Installation Guide

 

2

© 2005 HMS Industrial Networks.  

Installation Items Checklist

• Anybus-X 

ProfiBus

 to DeviceNet Gateway (part number AB7609).

• 

Anybus-X ProfiBus to DeviceNet Gateway User Manual

 downloadable from 

http://www.anybus.com  and go to the support section

• Power cable for connection to supplied 2 position connector.

• DeviceNet cable for connection to supplied 5 position connector.

• PROFIBUS cable for connection to 9-pin D-Subminiature connector.

• DeviceNet configuration tool such as RSNetworx for DeviceNet or NetTool-

DN.

• PROFIBUS configuration tool.

• EDS file, 

EDS_ABM_DEV_V_1_3.eds

, downloadable from:                           

http

://www.anybus.com  and go to the support section

.

• GSD file, HMS_1013.gsd, downloadable from 

http://www.anybus.com  and go 

to the support section

.

Installation and operating requirements

 

Power, input and output (I/O) wiring must be in 
accordance with Class 1, Division 2 wiring methods 
– article 501-4 (b) of the National Electric code, 
NFPA 70 and in accordance with local codes. 

 

Warning – Explosion Hazard

 – Substitution of 

components may impair suitability for class 1, 
Division 2.  

 

Warning – Explosion Hazard

 – When in hazardous 

locations turn off power before replacing or wiring 
modules. 

 

Warning – Explosion Hazard

 – Do not disconnect 

equipment unless power has been switched off or the 
area is known to be nonhazardous. 

 

Terminal tightening torque must be between 5 – 7 
lbs-in (0,5-0,8 Nm). 

 

For use in Class 2 circuits only. 

 

Suitable for Surrounding temperature of 65 C max. 

 

Use 60/75 C copper wire only. 

Содержание Anybus-X AB7609

Страница 1: ...Anybus X PROFIBUS to DeviceNet Gateway Installation Guide AB7609 Part no SP0847 Rev 1 10 ...

Страница 2: ...r 4 4 Setting the MAC ID and Baud Rate 4 Connecting to PROFIBUS 6 PROFIBUS Connector 6 Setting the PROFIBUS Network Address 6 Setting the PROFIBUS Baud Rate 6 Setting the PROFIBUS Network Termination 6 Configuration Port Connector 7 Further Technical Information 8 Technical Specifications 8 Environmental Specifications 8 EMC Directive Compliance 8 Electrical Specifications 8 Mechanical Rating 8 Wa...

Страница 3: ...e support section GSD file HMS_1013 gsd downloadable from http www anybus com and go to the support section Installation and operating requirements Power input and output I O wiring must be in accordance with Class 1 Division 2 wiring methods article 501 4 b of the National Electric code NFPA 70 and in accordance with local codes Warning Explosion Hazard Substitution of components may impair suita...

Страница 4: ...05 HMS Industrial Networks Connectors Connecting Power The Anybus X requires 24 volts DC power on the 2 position terminal block con nector DeviceNet Power Aux RS 232 PROFIBUS PROFIBUS Termination PROFIBUS Address 24VDC Common 24 VDC ...

Страница 5: ...sition terminal block connector A 120 ohm termination resistor not provided between CAN High and CAN Low may be required for proper network termination Setting the MAC ID and Baud Rate Factory default DeviceNet settings are MAC ID 63 Baud Rate 125K Red Net Power 24VDC Black Net Power 24VDC Common White CAN High Blue CAN Low CAN Shield ...

Страница 6: ... to the module Once the configuration has been down loaded the Anybus X will be reset automatically by the tool See the Configura tion section of the user manual for complete details on using BWConfig Setting MAC ID and Baud Rate Using a Node Commissioning Tool A DeviceNet node commissioning utility such as RSNetworx or NetTool DN may be used to change the MAC ID and baud rate settings Refer to th...

Страница 7: ... connector sets the 10 s digit The other switch sets the 1 s digit Hint If you look at the end of the Anybus X with the 9 pin D Sub PROFIBUS network connector on your left the node address is easier to read Setting the PROFIBUS Baud Rate The PROFIBUS baud rate is set during the configuration of the PROFIBUS Mas ter The Anybus X has automatic baud rate detection so no configuration of the Anybus X ...

Страница 8: ...g a null modem cable A null modem cable has pins 2 and 3 swapped so that the PC s Transmit line is connected to the Anybus X s Receive line and the PC s Receive line is connected to the Anybus X s Transmit line Note The Anybus X does not make use of the modem control signals specified for a DTE connector Connecting the module through devices such as isolation modules which assume control of these ...

Страница 9: ...nmental Specifications Operating Temperature 0 to 70 degrees Celsius Non Operating Temperature 25 to 85 degrees Celsius EMC Directive Compliance This product is tested to meet the Council Directive 89 336 EC Electromagnetic Compatibility EMC by applying the following standards in whole or in part documented in a technical construction file EN50081 2 EMC Generic Emission Standard Part 2 Industrial ...

Страница 10: ...N MERCHANTIBILITY FITNESS FOR A PARTICULAR PURPOSE TITLE AND NONINFRINGMENT THESE LIMITATIONS SHALL APPLY NOTWITHSTANDING THE FAILURE OF ESSENTIAL PURPOSE OF ANY LIMITED REMEDY PROVIDED IN THIS AGREEMENT NO AGENT OF HMS INDUSTRIAL NETWORKS AB IS AUTHORIZED TO INCUR WARRANTY OBLIGATIONS ON BEHALF OF HMS INDUSTRIAL NETWORKS OR TO EXPAND OR MODIFY THE LIMITATIONS SET FORTH HEREIN IN NO EVENT WILL HMS...

Страница 11: ...pport hms networks com Phone 46 0 35 17 29 20 Fax 46 0 35 17 29 09 Online www anybus com HMS America E mail us support hms networks com Phone 1 773 404 2271 Toll Free 888 8 Anybus Fax 1 773 404 1797 Online www anybus com HMS Germany E mail ge support hms networks com Phone 49 721 96472 0 Fax 49 721 964 7210 Online www anybus com HMS Japan E mail jp support hms networks com Phone 81 45 478 5340 Fax...