19 (48)
4.1.6
Communication Settings
The communication settings are configured by the INPUT1 and INPUT2 input pins in the
application interface. Invalid settings results in the Anybus CompactCom entering the state
EXCEPTION.
The Modbus address is configured using INPUT1. Valid range is 1 - 247.
Baud rate, stop bits, and parity are configured using INPUT2, as defined in the tables below.
INPUT2 bits 1..0 value
Stop bits, Parity
0
1, Even
1
1, Odd
2
2, None
3
1, None
INPUT2 bits 7..2 value
Baud rate
0 - 2
(reserved)
3
9600
4
19200
5
38400
6
57600
7
(reserved)
8
115200
9
625000
10 - 64
(reserved)