LED B - EtherNet/IP, Upper connector
LED C - Modbus TCP, Lower connector
Operation Status
EtherCAT
EtherNet/IP
Modbus TCP
PROFINET
Green, solid
EtherCAT device in
‘OPERATIONAL’-stat
EtherNet/IP online, one
or more connections
established
Modbus TCP online, at least
one message received
PROFINET online, one
or more connections
established
Red, solid
FATAL event
Duplicated EtherNet/IP IP
address
IP address conflict detected
FATAL event
Red, one flash
Unsolicited state change
Slave device application has
changed the EtherCAT state
autonomously.
N/A
N/A
Station name not set
Red, two flash
Sync Manager watchdog
timeout
N/A
N/A
IP address not set
Red, three flash
N/A
N/A
N/A
Expected Identification
differs from Real
Identification
Red, flashing
Invalid configuration
One or more connections
timed out
Connection timeout
One or more connections
timed out
Green/Red, flashing
EtherCAT RUN (green)
and ERROR (reed) LED
combined*
N/A
N/A
N/A
*The EtherCAT RUN (green) and ERROR (red) LED behaviors are combined in LED (C)/(D). This can cause LED (C)/(D) to alternate between red and
green. The LED behavior still represents the states described in the table above.
LED D - Security switch
Operation Status
Description
Off
No power/Security switch is unlocked/Exception/Fatal error
Green
Security switch is locked
Fatal Error and Exception Error
Fatal Error: A fatal error causes the Communicator firmware application to crash in an uncontrolled manner.
Exception Error: An exception error causes the Communicator to enter a controlled error state. The
Communicator firmware application is still running.
LED
Fatal Error
Exception Error
A
Red, solid
Red, solid
B
Red, solid
Off
C
Red, solid
Off
D
Off
Off
Anybus
®
Communicator
™
- EtherNet/IP
™
Adapter to Modbus TCP Server
Communicator LED Indicators
Page 42 of 56
SCM-1202-196 Version 1.0