LED 

No.

Description

Color

Function

1.

Service

Green

Flashing Green:

This node has an application but is not 

yet installed in a network (unconfi gured).

Off:

This node is confi gured and installed in a 

network.

Solid Green:

This node is unconfi gured and 

applicationless. Indicates errors detected 

by the Neuron Self-Test routine.

2.

Wink

Red

Off:

Normal state

Flashes Red: 

A wink command is received on the 

LonWorks network.

3.

Not used

-

-

4.

Module Status

Green/Red

Solid Green:

The module has been initiated correct 

and is working ok.

Flashes Red:

Software error. Restart the module.

Solid Red:

A hardware error has occurred.

5.

Modbus activity

Green/Red

Solid Red:

at start and if no Modbus messages have 

been received for more than 5 sec.

Solid Green:

after receiving correct Modbus message 

and correct start-up

6.

Confi g error

Green/Red

Solid Green:

Normal state

Flashes Red:

No confi guration saved in the gteway