About the Anybus X-gateway CANopen
7
Doc.Id. HMSI-168-91
Anybus X-gateway CANopen - PROFINET
Doc.Rev. 2.10
2.2 Status LEDs
The status LEDs on the front indicate the status of the module as shown in the table below. Their be-
havior is described in “Status LED Timing Diagrams” on page 47
Status LEDs 1 - 4 indicate the status of the primary PROFINET network and status
LEDs 5 - 6 indicate the status of the secondary CANopen (sub)network and the de-
vice.
#
State
Status
1 - Communication
Status
Off
Off line
Single flash, green
On-line, STOP (connection established, IO
controller in STOP state)
Green
On-line, RUN (connection established, IO
controller in RUN state)
2 - Module Status
Off
Not initialized
Green
No error, initialized
Single flash, green
Diagnostic data available
Double flash, green
Blink, used to identify the device
Single flash, red
Configuration error
Triple flash, red
No Station Name or no IP Address
assigned
Quadruple flash, red
Failed to initialize PROFINET IO
3 - Link/Activity
Off
No link
Green
Link established
Flickering green
Exchanging packets
4 - not used
-
5 - CANopen subnet
status
a
a. This LED shows the status of the secondary CANopen network.
Off
Power off
Flickering green/red
The LSS services are in progress
Blinking green
Preoperational state
Single flash, green
Stopped state
On, green
Operational state
Blinking red
Configuration error
Single flash, red
Warning limit reached in CAN controller,
e.g. bad or no signal on CANopen network
Double flash, red
Error control event
Triple flash, red
Sync error
Quadruple flash, red
Data communication timeout
Red
Bus off
6 - Device status
Off
Power off
Blinking green
Bootup
On, green
Running
Single flash, red
Initialization error
Double flash, red
Internal timeout
Triple flash, red
Hardware failure
Quadruple flash, red
Invalid switch settings
On, red
Fatal error
1
3
5
2
4
6