Additional configuration parameters should generally be left to their default value. They only
might need to be tuned in some very specific cases (installations with large number of units,
scenarios with large bursts of commands sent at
once …)
4.2.2
Signals
Select the Signals tab to configure the signals list (the Intesis
TM
internal points).
Figure 4.6
Signal list
1.
IU:
Indoor Unit identifier.
2.
Property
:
Identifies the different signals available per every MHI group. An
identification code is given to every different signal into the MHI group, identifying
every signal with an individual code. In section 2.2, an explanation of every signal
is given. A contextual menu appears using mouse right button click over the
column showing all the possible signal codes.
3.
Signal:
Signal's descriptive name (optional). Useful to identify the signal. The
default descriptive name corresponds to the signal's code, but can be edited or
modified.
4.
EIS:
KNX
data type (Data point) to encode the signal’s value. It will depend on
the MHI type of signal associated to it in every case. Edit using the mouse right-
button-click pop-up menu available on the column. Only the EIS defined in values
are allowed.
5.
Group:
Main KNX group address for the signal. Flags
R,W,T,U
explained below will
only apply for this main KNX group address, not for listening addresses. Formats
supported are P/I/S and P/S.
6.
Listening addresses:
KNX group addresses that will be listened by Intesis
TM
for
this signal. If Intesis
TM
receives a KNX telegram whose destination is one of these
listening addresses, the telegram will be taken into account and the corresponding
action will be performed on this signal (if W is active). Formats supported are
P/I/S and P/S, comma separated.
7.
Communication object flags:
7.1
R:
Indicates if this signal is allowed to be read from KNX system
(“R” flag
activated, “blank” flag not activated)
.