3.
Quick Start Guide
1.
Disconnect the air conditioning from the Mains Power.
2.
Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety
instructions given above and by the AC unit manufacturer).
3.
Connect the connection cable included with the interface between the interface and the
AC indoor unit following the instructions of the diagram.
4.
Connect the EIA-485 bus to the
interface’s
EIA485
connector.
5.
Close the AC indoor unit.
6.
Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation
’s
parameters (see section 4.3).
By default, the interface is set to:
▪
Modbus Slave Address
➔
1
▪
Modbus baud rate
➔
9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE:
All changes on the DIP-Switch configuration require a system power cycle to be
applied.
7.
Connect the AC system to Mains Power.
IMPORTANT:
The Intesis interface requires to be connected to the AC unit (powered) to
start communicating.
ON
ON
SW3
SW4