2.

 

Connection 

 
The interface comes with a specific cable and connectors to establish direct connection with the 
AC  indoor  unit.  It  comes  as  well  with  a  plug-in  terminal  block  of  2  poles  to  establish  direct 
connection with the Modbus RTU EIA-485 network. 
 

2.1

 

Connect to the AC indoor unit 

 
To  connect  the  INMBSMIT001I000  interface  with  the  AC  indoor  unit  you  must  follow  these 
steps: 
 
Disconnect  Mains  Power  from  the  AC  unit.  Open  the  front  cover  of  the  indoor  unit  to  have 
access  to  the  electronic  circuit.  Once  you  arrive  at  the  electronic  circuit,  locate  the  socket 
connector marked as 

CN105.

 

 
Take the cable that comes with the interface, insert one of its connectors (the one installed in 
the shortest uncovered part) into the socket of the INMBSMIT001I000, and the other connector 
(the one installed in the largest uncovered part) to the socket 

CN105

 of the AC unit's electronic 

circuit. You can place the INMBSMIT001I000 inside or outside the AC indoor unit depending on 
your needs. Remember that the INMBSMIT001I000 must also be connected to the Modbus RTU 
EIA-485 network. Close the AC indoor unit's front cover again to finish the connection. 

 

Do  not  modify  the  length  of  the  cable  supplied  with  the  interface,  it  may  affect  the  correct 
interface

’s operation

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

2.2

 

Connection to the EIA-485 bus 

 
Connect the EIA-485 bus wires to the plug-in terminal block of INMBSMIT001I000 (the one with 
two poles) and keep the polarity on this connection (A+ and B-). Make sure that the maximum 
distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are  not  allowed in the 
case of the EIA-485 bus. A terminator resistor of 120

 must be present at each end of the bus 

to  avoid  signal  reflections.  The  bus  needs  a  fail-safe  biasing  mechanism  (see  section  4.6  for 
more details).  
 
 
 

CN105 

AC indoor unit 

Electronic control board 

200 mm / 

7.9”

 

40 mm / 1.6”

 

Connection cable 
provided with the 
interface 
 

90 mm / 3.5”

 

EIA485 

A    B 

AC Unit 

53 mm / 2.1”

 

Use this hole to 
attach the cable 

using the staple 
and the screw 
provided with the 
interface

 

For  wall  mounting, 

extract the upper and 
lower  staples  until 
you listen the "click".

 

Fixing screw 

Modbus RTU 

EIA-485 

Bus

 

Содержание Intesis EIA-485

Страница 1: ...Compatible with Domestic Mr Slim and City Multi lines commercialized by Mitsubishi Electric USER MANUAL Issue date 12 2017 r22 ENGLISH...

Страница 2: ...s information is subject to change without notice URL https www intesis com 2 20 Modbus RTU EIA 485 Interface for Mitsubishi Electric air conditioners Compatible with Domestic Mr Slim and City Multi l...

Страница 3: ...d are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables a...

Страница 4: ...Quick Start Guide 7 4 Modbus Interface Specification 8 4 1 Modbus physical layer 8 4 2 Modbus Registers 8 4 2 1 Control and status registers 8 4 2 2 Configuration Registers 10 4 2 3 Considerations on...

Страница 5: ...required Direct connection to Modbus RTU EIA 485 networks Up to 63 INMBSMIT001I000 devices can be connected on the same network INMBSMIT001I000 is a Modbus slave device Direct connection to the AC in...

Страница 6: ...nic circuit You can place the INMBSMIT001I000 inside or outside the AC indoor unit depending on your needs Remember that the INMBSMIT001I000 must also be connected to the Modbus RTU EIA 485 network Cl...

Страница 7: ...e and the AC indoor unit following the instructions of the diagram 4 Connect the EIA 485 bus to the interface s EIA485 connector 5 Close the AC indoor unit 6 Check the DIP Switch configuration of the...

Страница 8: ...ion 4 2 1 Control and status registers Register Address protocol address Register Address PLC address R W Description 0 1 R W AC unit On Off 0 Off 1 On 1 2 R W AC unit Mode 1 0 Auto 1 Heat 2 Dry 3 Fan...

Страница 9: ...other error present see the table at the end of this document 22 23 R W Indoor unit s ambient temperature from external sensor at Modbus side 1 2 3 6 32768 Initialization value No temperature is being...

Страница 10: ...ption 12 13 R W AC Model 13 14 R W Open Window switch off timeout 9 0 30 minutes Factory setting 30 minutes 14 15 R Modbus RTU baud rate 2400bps 4800bps 9600bps Default 19200bps 38400bps 57600bps 7680...

Страница 11: ...rovide directly a temperature to be used as a reference of the control loop of the AC indoor unit In order to overcome this limitation and enable the usage of an external temperature sensor e g from M...

Страница 12: ...tpoint s value shown by the Remote Controller or other Control System from Mitsubishi connected to the indoor unit may show a different value from the value shown in register 4 5 The User is not be ab...

Страница 13: ...rks S L U All rights reserved This information is subject to change without notice URL https www intesis com 13 20 Fahrenheit value Value in Modbus register is the temperature value in Fahrenheit i e...

Страница 14: ...e following locations The following tables apply to the interface s configuration through DIP switches SW1 AC indoor unit s features SW1 P1 4 Description Not used Default value Not used Not used Defau...

Страница 15: ...EIA 485 termination resistor Table 4 3 SW4 Temperature and termination resistor configuration SW4 P1 2 4 Description Temperature values in Modbus register are represented in degrees x1 Default value...

Страница 16: ...s Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 17: ...s ON 2s OFF Device correctly configured and working During normal operation LED OFF OFF continuously No Modbus Slave address configured During normal operation LED blinking 200ms ON 200ms OFF Communic...

Страница 18: ...tage signals For terminal solid wires or stranded wires twisted or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x...

Страница 19: ...subject to change without notice URL https www intesis com 19 20 6 List of supported AC Unit Types A list of Mitsubishi Electric indoor unit model s references compatible with INMBSMIT001I000 and its...

Страница 20: ...t of compressor 4220 Voltage anomaly 4230 Radiator panel temperature anomaly TH8 5101 Ambient temperature probe anomaly TH1 indoor unit 5102 Liquid probe anomaly TH2 5102 Cond Evap probe anomaly TH5 5...

Отзывы: