Installation Instructions for 

HMI

 HOYME 

Adaptor 0244-05A  

Control Centre for One Furnace with Two Thermostats heating/cooling Two Separate Zones   

 

 
INSTALLATION OF THIS ADAPTOR SHALL BE 
IN ACCORDANCE WITH THE REQUIREMENTS 
OF THE AUTHORITIES HAVING JURISDICTION

 

 
Refer also to HOYME Installation Instructions 
for Replacement/Ventilation Air Control 
Damper, Series HAC. 

 
                 ADP-0244-05A  
  

 

           

     

                           

4” x 5” x 2 1/2” 

                        101 x 127 x 64 mm 
  
This Relay Adaptor (x2) is to be used in 

tandem

 

as a control centre to operate 

one furnace

 with 

two separate thermostats

 to heat and cool

 two 

separate zones

 in a building. 

Two

 24Vac

 P

ower 

C

lose 

dampers

 are also required. (See wire 

diagrams on page 2) 

 

 

Two-damper zone control operation: 

Two Air Control Dampers are required and are to 
be in the normally open position so that air from 
the furnace fan supplies air simultaneously to both 
zones. At such time as heating/cooling is required 
to a zone, the damper to the other zone closes 
thus allowing air to continue flowing to the zone of 
attention. If both zones ask for attention, both 
dampers remain open. At no time are both 
dampers closed while the furnace circulating fan 
is running. The call for air conditioning overrides 
the call for heat.  
  

Fitness of this Adaptor/Damper combination, 
to satisfy air supply requirements for fuel fired 
appliances during operation of the 

 

 

 
Inter-connected exhaust fan(s), shall be  
investigated by the enforcing authorities. 

 
If an intake air duct is required, installation shall 
be in accordance with: In Canada - CAN/CSA 
B149 & B139; In the USA – ANSI/NFPA 54, 2006, 
ANSI Z223.1 and/or local codes including local 
codes relating to ventilation air duct installation.  

 

 

I.D.: ADP-0244-05A.

  (

Two required

Each Adaptor comes with four 24Vac relays: 
2 – DPDT, Coil 24Vac. Pts 24Vac-5 Amps. 
2 – SPDT, Coil 24Vac. Pts 24Vac-5 Amps 
 

General Installation: 

 
- Refer to local and applicable codes. 
- If an auxiliary transformer is required, use an 
approved 24Vac transformer of adequate 
capacity. 
- Supply for the transformer primary shall be    
taken from the line voltage supply of the  
appliance.   
- Always conduct a thorough check-out after  
installation is complete. 
- Affix appropriate labels and follow  
instructions and warnings on each label. 
 

Adaptor Installation: 

 
1. Turn off the power to the furnace. 
2. Place adaptors side by side in the area of the 
furnace and identify each adaptor with each zone.  
3. Connect each zone thermostat to its own 
adaptor as per wiring diagram. 
4. Note: Connect each adaptor to each other with 
terminal #1 to terminal #2 of the other.  
5. Connect each adaptor to the furnace terminals 
as per wiring diagram. 
 

Two zone damper installation

: Before installing 

dampers, test for operation to power close with 
24Vac supply.  
 

Note:

 Zone dampers are to be sized so that the 

air flow capacity of either damper does not 
overload the air flow capacity of the furnace fan. If 
necessary, use an atmospheric pressure damper 
as a bypass. 