HK Instruments PS Series Скачать руководство пользователя страница 1

Copyright HK Instruments 2018

www.hkinstruments.fi

Installation version 6.0 2018

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE SWITCHES 

PS Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank  you  for  choosing  an  HK  Instruments  PS  series  differential 
pressure switch. The PS series is intended for use  in commercial en

-

vironments. It is designed with field selectable setpoint adjustment 
to meet your application requirements.

The PS series differential pressure switches is comprised of PS300 
with  range  from  30...300  Pa,  PS500  with  range  from  30...500 
Pa,  PS600  with  range  from  40...600  Pa,  PS1500  with  range  from 
100...1500 Pa and PS4500 with range from 500...4500 Pa.

PS series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring
• valve and damper monitoring

SPECIFICATIONS

Performance

Accuracy (at applied pressure)

At low limit (Typical):

PS200: ± 5 Pa

PS300: ± 5 Pa

PS500: ± 5 Pa

PS600: ± 5 Pa

PS1500: ± 20 Pa

PS4500: ± 100 Pa

At high limit (Typical):

PS200: ± 20 Pa

PS300: ± 30 Pa

PS500: ± 30 Pa

PS600: ± 50 Pa

PS1500: ± 50 Pa

PS4500: ± 200 Pa

Switching differential:

PS200: 20 Pa

PS300: 20 Pa

PS500: 20 Pa

PS600: 30 Pa

PS1500: 80 Pa

PS4500: 250 Pa

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 50 kPa

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Pa

Measurement range:

PS200: 20-200 Pa

PS300: 30-300 Pa

PS500: 30-500 Pa

PS600: 40-600 Pa

PS1500: 100-1500 Pa

PS4500: 500-4500 Pa

Environment:

Operating temperature: -20...60 °C

Storage temperature: -20...85 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 105 x 73 x 63 mm

Weight: 

150 g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:  

Case: ABS

Cover: PC

Membrane: Silicone

Duct connectors: ABS

Tubing: PVC

Protection standard: 

IP54 

Electrical connections:

3 screw terminals

Wire: 12–24 AWG (0.2–1.5 mm2)

Cable entry:

Strain relief: M16

Knockout: 16 mm

Pressure fittings:

Male ø 5.0 mm

Electrical

Input: 

24–250 VAC

Output: 

NO / NC circuit

Electrical rating, resistive load:

3 A / 250 VAC (PS200: 0.1 A / 250 VAC)

Electrical rating, inductive load:

2 A / 250 VAC (PS200: -)

Conformance

Meets requirements for CE marking:

RoHS Directive 2011/65/EU

LVD Directive 2014/35/EU