background image

Copyright HK Instruments, Inc. 2017

www.hkinstrumentsinc.com

Installation version 2.0 2017

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE GAUGES

& MANOMETERS – MM Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO 

INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions can result in 

PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect power before 

installing or servicing and use only wiring with insulation rated for full device 
operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially flammable or 

explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system whose 

specifications and performance characteristics are not designed or controlled 
by HK Instruments. Review applications and national and local codes to assure 
that the installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments MM Series liquid col-
umn manometer. The MM Series is intended for use in commercial 
environments for air and non-corrosive gases. The MM Series is 
designed with overpressure reservoir to protect the manometer 
liquid from leaking into the duct during over pressure.

The MM Series includes a field adjustable zero point calibration 
and pressure limit stickers. The MM Series is available with op-
tional level bubble and NIST standard calibration certificates.

SPECIFICATIONS

Performance

Accuracy:

MM-0202    

±0.004 inWC

MM-04  

 

±0.004 inWC

MM-0420

-0.4–0 inWC  

±0.02 inWC

0–2.0 inWC  

±0.1 inWC

MM-00824

0–0.8 inWC  

±0.02 inWC

0.8–2.4 inWC  

±0.1 inWC

Overpressure:

Max Pressure: 800 inWC (200 kPa)

Technical Specifications

Media Compatibility:

Dry air or non-aggressive gases

Measuring units:

inWC

Measuring ranges:

-0.2–0–0.2 inWC
0–0.4 inWC
-0.4–0–2.0 inWC
0–0.8–2.4 inWC

Environment:

Operating temperature:
-40–140 °F (-40–60ºC)

Gauge fluid:

Red: s.g. 49.068 lb/ft3 (0.786 kg/dm

3

) (15 °C)

(Isopar M)

MM-0202 RED
MM-04 RED
MM-0420 RED
MM-00824 RED

Physical

Case:

ABS

Cover:

PMMA

Knobs:

Polycarbonate (PC)

O-ring:

Nitrile rubber (NBR)

Weight

14.82 oz (420 g)

Safety

Product equipped with integral reservoir to prevent 
gauge fluid leakage during overpressure situation.

Product is tested and meets the NRTL product approval
requirements.

INTRODUCTION

WARNING

AVERTISSEMENT

• LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE PROCÉDER À 

L’INSTALLATION, LA MISE EN SERVICE OU L’ENTRETIEN DE CET APPAREIL.

• Le non-respect des informations et instructions de sécurité peut entraîner DES 

DOMMAGES CORPORELS, LA MORT ET/OU DES DÉGÂTS MATÉRIELS.

• Afin d’éviter les chocs électriques et les dommages matériels, déconnectez 

l’alimentation électrique avant l’installation ou l’entretien, et utilisez uniquement du 
câblage avec isolement assigné pour une tension d’alimentation optimale.

• Afin de prévenir les risques d’incendie et/ou d’explosion, n’utilisez pas l’appareil 

dans des environnements potentiellement inflammables ou explosifs.

• Conservez ces instructions à titre de référence.
• Une fois installé, ce produit fera partie d’un système technique dont les 

spécifications et les caractéristiques de performance ne sont ni conçues ni 
contrôlées par HK Instruments. Consultez les applications et les codes nationaux 
et locaux pour garantir le fonctionnement correct et sûr de l’installation. Ne faites 
appel qu’à des techniciens expérimentés et compétents pour installer cet appareil.

APPLICATIONS

MM series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring
• pressure monitoring in cleanrooms