Copyright HK Instruments 2022

www.hkinstruments.fi

Installation version 8.0 2022

INSTALLATION
INSTRUCTIONS

Pressure and flow controllers 
DPT-Ctrl-MOD Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO 

INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions can 

result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect power 

before installing or servicing and use only wiring with insulation rated for 
full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system whose 

specifications and performance characteristics are not designed or 
controlled by HK Instruments. Review applications and national and local 
codes to assure that the installation will be functional and safe. Use only 
experienced and knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPT-Ctrl-MOD series air han-
dling  controller  with  differential  pressure  or  airflow  transmitter.  The  DPT-
Ctrl-MOD series PID controllers are engineered for building automation in 
the HVAC/R industry. With the built-in controller of the DPT-Ctrl-MOD it 
is possible to control the constant pressure or flow of fans, VAV systems or 
dampers. When controlling air flow, it is possible to select a fan manufacturer 
or a common measuring probe that has a K-value.

The DPT-Ctrl-MOD includes an Input terminal that enables the reading of 
multiple  signals  such  as  temperature  or  control  relays  over  Modbus.  The 
Input terminal has one input channel designed to accept 0−10 V, NTC10k, 
Pt1000, Ni1000/(-LG), and BIN IN (potential free contact) signals.

DPT-Ctrl-MOD series devices are commonly used in HVAC/R

systems for:

• Controlling differential pressure or air flow in air handling systems

• VAV applications

• Controlling parking garage exhaust fans

SPECIFICATIONS

Performance

Accuracy (from applied pressure):

Model 2500:

Pressure < 125 Pa = 1 % + ±2 Pa

Pressure > 125 Pa = 1 % + ±1 Pa

Model 7000:

Pressure < 125 Pa = 1.5 % + ±2 Pa

Pressure > 125 Pa = 1.5 % + ±1 Pa

(Accuracy specifications include: general accuracy, 

linearity, hysteresis, long term

stability, and repetition error)

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Manual pushbutton or Modbus

Response time:

1.0−20 s, selectable via menu or Modbus

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format (11 bits) in RTU mode:

 

Coding system: 8-bit binary

 

Bits per byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent  

 

 

first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration

Modbus address: 1–247 addresses selectable in 

configuration menu

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Controller parameter (selectable via menu and 
Modbus):

Setpoint 0...2500 (model 2500)

 

0...7000 (model 7000)

P-band   0...10 000

I-gain   0...1000 

D-factor 0...1000

Pressure units (selectable via menu):

Pa, kPa, mbar, inWC, mmWC, psi

Flow units (selectable via menu):

Volume: m

3

/s, m

3

/hr, cfm, l/s

Velocity: m/s, ft/min

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -20...50 °C

Temperature compensated range 0...50 °C

Storage temperature: -40...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions:

Case: 102.0 x 71.5 x 36.0 mm

Weight:

150 g

Mounting:

2 each 4.3 mm screw holes, one slotted

Materials:

Case: ABS

Lid: PC

Pressure inlets: Brass

Protection standard:

IP54

Display

2-line display (12 characters/line)

 

Line 1: Direction of control output

 

Line 2: Pressure or air flow measurement,  

 

 

selectable via menu

 

 

If input is selected, line 2 shows also

 

 

input information (for example  

 

 

temperature)

Size: 46.0 x 14.5 mm

Electrical connections:

4+4 position spring-loaded terminals

Wire: 0.2–1.5 mm

2

  (16–24 AWG)

Cable entry:

Strain relief: M16

Knockout : 16 mm

Pressure fittings

5.2 mm barbed brass

+ High pressure

− Low pressure

Electrical

Supply voltage:

24 VAC or VDC, ±10 %

Power consumption:

< 1.0 W

Output signal:

via Modbus

Control output:

0-10 V

Input signal:

0−10 V, NTC10k, Pt1000, Ni1000/(-LG) or BIN IN

Conformance

Meets the requirements for:

 

 

CE:   

UKCA:

EMC: 

  

2014/30/EU 

S.I. 2016/1091

RoHS:    

2011/65/EU 

S.I. 2012/3032

WEEE:   

2012/19/EU 

S.I. 2013/3113

INTRODUCTION

WARNING

APPLICATIONS

RoHS

COMPLIANT

Содержание DPT-Ctrl-MOD Series

Страница 1: ...ed pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 25 kPa Burst pressure 30 kPa Zero point calibration Manual pushbutton or Modbus Response time 1 0 20 s selectable via menu or Modbu...

Страница 2: ...o a fan with pressure measurement taps Select Common probe when using DPT Ctrl MOD with a common measurement probe that follows the formula q k P i e FloXact MANUFACTURER Common probe SELECT UP DOWN Common probe Flakt Woods SELECT UP DOWN STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable s 2 Connect the wires as...

Страница 3: ... 10 V D VALUE 1 00 SELECT UP DOWN 15 Push the select button to exit menu SELECT EXIT MENU SELECT 12 Select proportional band according to your application specifications P VALUE 206 SELECT UP DOWN 13 Select integral gain according to your application specifications I VALUE 4 00 SELECT UP DOWN 14 Select derivation time according to your application specifications STEP 6 TEMPERATURE COMPENSATION The...

Страница 4: ...0 99 4x0021 Temp comp drop decimal part 16 bit 0 999 0 0 0 999 4x0022 PID Pressure Ref SP 1 16 bit 250 2500 model 2500 700 7000 model 7000 250 2500 model 2500 700 7000 model 7000 4x0023 PID Pressure Ref SP 2 16 bit 250 2500 model 2500 700 7000 model 7000 250 2500 model 2500 700 7000 model 7000 4x0024 PID Flow Ref SP 1 integer 16 bit 0 30000 0 30000 4x0025 PID Flow Ref SP 1 decimal 16 bit 0 999 0 9...