HK Instruments DPT-CR-MOD Series Скачать руководство пользователя страница 1

Copyright HK Instruments 2022

www.hkinstruments.fi

Installation version 1.0 2022

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 

DPT-CR-MOD Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPT-CR-MOD series dif-
ferential pressure transmitter. DPT-CR-MOD series is designed spe-
cially for cleanroom monitoring. In addition to differential pressure, 
the device enables monitoring temperature and relative humidity.

A 0…10 V voltage input of an external humidity and temperature 
transmitter can be connected to the input terminal of the device. In 
this case, all three measured values (differential pressure, relative 
humidity, temperature) will be shown simultaneously on the display. 
Alternatively, a passive temperature sensor can be connected to the 
input terminal.

DPT-CR-MOD  is  compatible  with  Modbus  serial  communication 
protocol.

DPT-CR-MOD series devices are commonly used in HVAC/R

systems for:

•  pressure, temperature and humidity monitoring in cleanrooms

SPECIFICATIONS

Performance

Measurement range:

-250...2500 Pa

Accuracy (from applied pressure):

 

Pressure < 125 Pa = 1 % + ±2 Pa 

Pressure > 125 Pa = 1 % + ±1 Pa 

 

(Including: general accuracy, linearity,

hysteresis, long term stability and repetition error)

Input accuracy:

 

Temperature: ±0.25 °C typical @ 25 °C + accuracy of 

external transmitter

Humidity: ±0.5 % rH typical @ 25 °C + accuracy of

external transmitter

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Manual pushbutton or via Modbus

Response time:

1...20 s selectable via menu

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format (11 bits) in RTU mode:

 

Coding System: 8-bit binary

 

Bits per Byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent  

 

 

first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration

Modbus address: 1−247 addresses selectable in

configuration menu

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Selectable via menu (Pa, mbar, inchWC, mmWC, psi)

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -20...50 °C

Temperature compensated range 0...50 °C

Storage temperature: -40...70 °C

Humidity: 0 to 95 % rH, non-condensing

Physical

Dimensions: 

Case: 102 x 71.5 x 36 mm 

Weight: 

150 g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:   

Case: ABS

Lid: PC 

Pressure inlets: Brass

Protection standard: 

IP54

Display:

2-line display (12 characters/line)

Line 1: pressure measurement

Line 2: relative humidity and temperature (if external

measurements are connected)

Electrical Connections:

4+4 spring load terminals, max 1.5 mm

2

Cable entry: M20

Pressure fittings:

Male ø 5.2 mm

+ High pressure

- Low pressure

Electrical

Supply voltage: 

24 VAC or VDC ± 10 %

Power consumption:

< 1.3 W

Output signal:

via Modbus

Input signals:

Temperature input: 0−10 V or NTC10k, Pt1000,

Ni1000/(-LG)

RH input: 0−10 V

 

Conformance

Meets requirements for:

 

 

CE:   

UKCA:

EMC: 

 

2014/30/EU 

S.I. 2016/1091

RoHS:   

2011/65/EU 

S.I. 2012/3032

WEEE:   

2012/19/EU 

S.I. 2013/3113

INTRODUCTION

APPLICATIONS

WARNING

RoHS

COMPLIANT

Содержание DPT-CR-MOD Series

Страница 1: ...y monitoring in cleanrooms SPECIFICATIONS Performance Measurement range 250 2500 Pa Accuracy from applied pressure Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Including general accuracy linearity hysteresis long term stability and repetition error Input accuracy Temperature 0 25 C typical 25 C accuracy of external transmitter Humidity 0 5 rH typical 25 C accuracy of external transmitter Overpres...

Страница 2: ...for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections DPT 4 3 DPT Display connection A 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal block...

Страница 3: ...ample 2 rH Temp transmitter connected to DPT CR MOD rH Temp transmitter rH 0 10 V Jumper settings Temp 0 10 V 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 9 Push the se...

Страница 4: ...pair of a defective part or device or if needed a new part or device but not installation or exchange costs Under no circumstance is the seller liable for damages compensation for indirect damage Register Parameter description Data Type Value Range 3x0001 Program version 16 bit 0 1000 0 00 99 00 3x0002 0004 Not in use 3x0005 Temperature Celsius Pt1000 16 bit 500 500 50 0 50 0 C 3x0006 Temperature ...