HK Instruments DPG Series Скачать руководство пользователя страница 1

Copyright HK Instruments, Inc. 2017

www.hkinstrumentsinc.com

Installation version 2.0 2017

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE GAUGES

& MANOMETERS – DPG Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO 

INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions can result in 

PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect power before 

installing or servicing and use only wiring with insulation rated for full device 
operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially flammable or 

explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system whose 

specifications and performance characteristics are not designed or controlled 
by HK Instruments. Review applications and national and local codes to assure 
that the installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPG Series differential 
pressure gauge. The DPG Series is intended for use in commercial 
environments in HVAC/R applications. It is designed to detect air 
and non-corrosive gas pressures (differential and positive) and to 
provide a clear analog display of the measured values.

The DPG Series includes field adjustable zero point calibration and 
overpressure protection. The DPG Series is available with NIST 
standard calibration certificates.

SPECIFICATIONS

Performance

Accuracy:

<±2 % F.S (at 67 °F)

Overpressure:

Burst pressure: 80 inWC (20 kPa)

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

inWC

Measurement ranges:

0–1.0 inWC
0–2.0 inWC
0–3.0 inWC
0–5.0 inWC
0–10.0 inWC
0–15.0 inWC
0–20.0 inWC

Environment:

Operating temperature: 23–140 °F (-5–60 °C)
Storage temperature: -40–185 °F (-40–85 °C)

Physical

Case:

ABS

Cover:

PC

Membrane:

Silicone

Machinery:

Aluminum and steel spring

Unit mounting diameter

ø 4-11/32 in (110 mm)

Weight:

8.25 oz (234 g)

INTRODUCTION

WARNING

AVERTISSEMENT

• LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE PROCÉDER À 

L’INSTALLATION, LA MISE EN SERVICE OU L’ENTRETIEN DE CET APPAREIL.

• Le non-respect des informations et instructions de sécurité peut entraîner DES 

DOMMAGES CORPORELS, LA MORT ET/OU DES DÉGÂTS MATÉRIELS.

• Afin d’éviter les chocs électriques et les dommages matériels, déconnectez 

l’alimentation électrique avant l’installation ou l’entretien, et utilisez uniquement du 
câblage avec isolement assigné pour une tension d’alimentation optimale.

• Afin de prévenir les risques d’incendie et/ou d’explosion, n’utilisez pas l’appareil 

dans des environnements potentiellement inflammables ou explosifs.

• Conservez ces instructions à titre de référence.
• Une fois installé, ce produit fera partie d’un système technique dont les 

spécifications et les caractéristiques de performance ne sont ni conçues ni 
contrôlées par HK Instruments. Consultez les applications et les codes nationaux 
et locaux pour garantir le fonctionnement correct et sûr de l’installation. Ne faites 
appel qu’à des techniciens expérimentés et compétents pour installer cet appareil.

APPLICATIONS

DPG series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring
• monitoring static pressure

RoHS 2

2011/65/EU

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =