1. Features 

 

Can detect level of various solids and powders 

 

Can be fully operated for powders of low and high densities. 

 

Can detect the intrface of sediments in the liquid. 

 

Has a longer lifetime since it has no mechanical movements. 

 

Does not need adjustments after installation. 

 

 

2. Specifications 

Body 

Steel (SS41) 

Protection 

IP65 

Range of Environment Temp. 

-20°C ~ + 60°C 

Mounting Material 

Stainless Steel (SUS 304) 

Mounting Specification 

3/4" PT (KSB0222) 

Operating Temp.(Inside Vessel) 

-20°C ~ + 250°C 

Max. Pressure 

10 kgf/cm

2

 

Combination Unit 

HLC-901 

Power Supply 

AC 110 V / 220 V 60 Hz±  10% 

Power Consumption 

Approx. 5 VA 

Sensitivity 

Over 0.2(Specific Gravity) 

 

Max. AC 250 V, 5 A 

Relay Output 

Max. DC 28 V, 5 A 

 

(Relay 1 SPDT) 

 

When relay is on. 

Indication of Switch 

When detection LED is off. 

 

When detection LED becomes RED. 

Painting 

Metallic silver 

Distance Between Sensor and unit 

Max. 300 m 

Cable 

twisted paired cable 

 

 

3. Operating Principle 

HITROL’s HTM is an innovative, multipurpose switch and has the simplest structure. 

HTM sensor head is composed of one module which has an oscillating coil generating frequency 

and a sensing coil detecting oscillation. 

When  the  material  inside  the  vessel  does  not  exist  around  the  sensing  rod,  the  sensing  rod 

continuously vibrates due to the oscillating coil. 

Содержание HTM-930

Страница 1: ... 01 Page 1 7 HITROL CO LTD HEAD OFFICE FACTORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 943 5600 www hitrol com INSTRUCTION MANUAL VIBRATION TYPE LEVEL SWITCHES HTM 930 Series ...

Страница 2: ... no HTM 930 M_Kor_2016 Rev 0 Issued date 2016 01 Page 2 7 Table of Contents 1 Features 3 2 Specifications 3 3 Operating Principle 4 4 Dimensions 3 5 Installation Method 4 6 Wiring Method 4 7 Maintenance 5 ...

Страница 3: ... cm2 Combination Unit HLC 901 Power Supply AC 110 V 220 V 60 Hz 10 Power Consumption Approx 5 VA Sensitivity Over 0 2 Specific Gravity Max AC 250 V 5 A Relay Output Max DC 28 V 5 A Relay 1 SPDT When relay is on Indication of Switch When detection LED is off When detection LED becomes RED Painting Metallic silver Distance Between Sensor and unit Max 300 m Cable twisted paired cable 3 Operating Prin...

Страница 4: ...ists around the sensing rod the vibration frequency is significantly reduced and the output from the sensing coil is decreased to a very low value It is operated using the above mentioned operation principle and when a signal is supplied to alarm and or process control 4 Dimensions Controller Sensor ...

Страница 5: ...ed to the ground 6 Wiring Method 6 1 HLC 901L 1 Refer Fig 2 Fig 2 1 Schematic diagram for wiring 2 Two wire twisted shield cable should be used when wiring sensor and the unit HITROL s standard length is 6 m However when the distance between the sensor and the unit is over 6 m it is required to consult cable specification to HITROL 3 When wiring between the sensor and the unit the separate cable c...

Страница 6: ...ring between the sensor and the unit the separate cable conduits should be used for power and sensor signal 4 It should be grounded for either the sensor or the units 5 The sensitivity can be adjusted using DEG If it is dialed counterclockwise the vibration becomes weak and the sensitivity becomes high But if clockwise the vibration becomes strong and the sensitivity becomes low 7 Maintenance It i...

Страница 7: ... Rev 0 Issued date 2016 01 Page 7 7 HITROL CO LTD HEAD OFFICE FACTORY R D INSTITUTE 141 Palhakgol gil 98 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 031 950 9700 FAX 031 950 9796 9 http www hitrol com hitrol hitrol com ...

Отзывы: