HNV-970 Series 

   

                                                                                                                  HITROL CO., LTD.                                             

          6   

                                                                                                                                                                                         

Precautions 
for Mounting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

For the mounting of vibration level switch, Screw and Flange (ANSI, JIS and DIN) types 

are available and installation with various mounting type is available. Below points shall 

be considered when installation of the product.       

 

Side Installation (Horizontal Installation) 

The product is not much affected by the material build-up on the sensor but it can be sensitive 

by shock due to thin sensing part. So, if possible, it is not recommended to install where the 

medium is falling down. However, if it is unavoidable to install at the inlet, protector shall be 

installed to prevent a sensing part from damage by falling medium. 

 

Top Installation (Vertical Installation) 

Special precautions are not required. It is generally used to detect an interface level of 

sediment in liquids. 

 

■  When side installation, inactive rod shall be exposed min. 50mm at least into the tank 

inside and it is recommended to install slopingly (about 15

o

) against a horizontal line 

in order to prevent a malfunction by foreign substance between nozzle and probe.   

■  Sensor shall be installed at the place far from inlet of the tank and protector shall be 

installed in order to protect the sensor from damage. 

■  When side installation, cable entry shall be installed facing the ground for rain proof. 

■  When the installation at outside, it is recommended to install a sun cover in order to 

avoid an effect caused by temperature rise.   

■  If there is an agitator in  the tank, the probe shall be installed with a safe distance 

from the agitator.     

 

Pay more attention for installation to the tank which has a vibration because 

it may cause a malfunction.

   

INTERFACE 

Sediment

Liquid 

Содержание HLC-970-L

Страница 1: ...ACTORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 950 9796 9799 www hitrol com INSTRUCTION MANUAL Vibration Type Level Switch HNV 970 Series Doc no HNV970_IM_Eng_Rev 0 Issue date 2021 03 ...

Страница 2: ...g 7 Operating 7 Precautions for Installation 8 Precautions for Removal 8 Safety and Environment 8 Maintenance 8 Precautions for transportation assembly 8 Failure Check 9 Marking 9 Warranty and Contact Information 9 You should be well informed of the contents where WARNING is marked before carrying out the work You should be careful where CAUTION is marked to carry out the work ...

Страница 3: ...is sensed by the control unit and relay signal is out It can be generally used for alarm and process control Various kinds of solid or powder level can be detected Used to detect an Interface level of sediments such as sand and carbon etc in liquids Long life cycle due to mechanical moveless parts Length extension is available HNV 970 Series is a level switch which detects powder and liquid in the...

Страница 4: ... Mounting Screw Flange Wetted Part Material 316L SS Process Connection PT 1 M Installation Side Top Distance Max 500m between sensor and unit Model HLC 970 L Housing Cable Entry AL C 2 PF 3 4 F Enclosure Weather Proof IP65 Ambient Temperature 20 60 Installation Local Power Source AC 110V AC 220V DC 24V Contact Form DPDT Contact Rating AC 250V 5A DC 30V 5A Sensor Combination Unit ...

Страница 5: ...HNV 970 Series HITROL CO LTD 5 Dimensions HNV 970 HLC 970 L ...

Страница 6: ...not required It is generally used to detect an interface level of sediment in liquids When side installation inactive rod shall be exposed min 50mm at least into the tank inside and it is recommended to install slopingly about 15o against a horizontal line in order to prevent a malfunction by foreign substance between nozzle and probe Sensor shall be installed at the place far from inlet of the ta...

Страница 7: ...nit is 500 meter Power and LOW MIDDLE SENSITIVITY LEDs are on when the power is supplied When the medium is detected LOW MIDDLE SENSITIVITY LEDs are off and Relay LED is on No need separate setting by user because it is basically set by factory If the setting at the site is newly required adjust VR1 and VR2 to LEDs to be off and adjust VR1 until Red LED of LOW SENSITIVITY is on After that adjust S...

Страница 8: ...echanical damage to the sensor If the measuring medium is so sticky check if the medium is stuck on the sensor and remove it periodically The material stuck on the sensor may cause a malfunction and damage to the device Precautions for Use Make sure to mount the product to a vessel using required tools for sure as tightly as possible Do not apply high impact to the product Precautions for Wiring M...

Страница 9: ...Gyeonggi Do Korea Tel 82 31 950 9700 Headquarter and After Sales Service Team Fax 82 31 943 5600 Headquarter and After Sales Service Team Product Identification The product identification mark is attached on the housing and shows the model name serial number working temperature working pressure and matters regarding output The serial number is a unique manufacturing number for the identification o...

Отзывы: