HCC(HPC)-96RF-R Series
HITROL CO., LTD. 8
■ Connection of HCC-96RF-R(Sensor) and HLC-96RF-R(Controller)
- Prepare the cable (CVVS 3C) that connects the sensor and combination unit and connect as
shown below. (The distance between HCC-96RF-R and HLC-96RF-R is available up to 500m.)
■ Power Connection
- The power specification of the instrument consists of AC 110V or 220V, which
energizes the sensor power supply.
- Be sure to check the following items before wiring:
Is the specified power voltage used?
Has the CCVS wires been used for the wires between the controller and the amplifier?
Are separate conduits other than power lines used when the controller and amplifier are engaged?
■ Output Connection
- The contact capacity of relay is AC 250V, 5A / DC 30V, 5A, and larger capacity values
require connecting external relay.
■ Initial / General Adjustment
1. Set the
Fine
variable resistor to 0%.
2. Turn the
Coarse
variable resistor clockwise 18 times.
3. Slowly rotate the
Coarse
variable resistor clockwise until the detect LED changes from
yellow to red.
4. Rotate clockwise or counter-clockwise, repeat the detect LED to operate from red to
yellow or from yellow to red 3 times, then set it at the point where the yellow light is on.
5. Moving the
Fine
variable resistor from 0% to 10% indicates setting at ultra-high
sensitivity (∠c 1pF).
6. From now on, turn the
Fine
variable resistor to set according to the dielectric ratio of
the measuring instrument.
Wiring
Settings