HCC(HPC)-96RF-R Series
HITROL CO., LTD. 7
■ Side Mounting Installation
- If the content has the characteristics of creating an excess sediment layer, the product
shall be installed at an angle of about 45 degrees.
- If the content has a high density, a protector shall be installed at least 200mm above
from the probe in order to protect the probe.
■ Top Mounting Installation
- If the probe length is more than 1000mm, install a fixed bracket insulated at the bottom.
- Sensing probe shall be installed at least 500mm away from the side of tank.
- If more than one level switch is installed in a container, the distance between each probe
shall be at least 300mm apart. (If the distance between probes is short, it may be
affected by the interconnection of the instrument, causing unstable operation.)
- For side mounting installations, an inactive rod shall be exposed to the inside of the tank
by at least 50mm, and it is recommended that the probe be tilted by 15 degrees to the
horizontal surface. (A foreign object may cause malfunction between the nozzle and the probe)
- Probe shall be installed to avoid the inlet side of the measuring instrument, and the
protector shall be installed to prevent damage to the probe.
- For side mounting installations, the entrance to the electric wire shall be installed facing
the ground to maintain the waterproof function.
- When installing on the low level, carefully install the dead stock and the material bridge.
- For outdoor installations, it is recommended to install the sun cover to avoid the effects
of temperature increases.
- In case of tank with stirrer, the probe shall be installed at a safe distance from the stirrer.
Installation
Precautions
for
Installation