CLVBA-CLVA

 

EVAPORATION UNITS AIR-AIR  

INTRODUCTION 

 

Incorrect Operation 
 

In case of breakdowns or operation faults, turn the unit off. 
 

Periodic Inspections and Maintenance 
 

 

Carry out periodic inspections to detect possible damaged or broken parts. If these parts are not repaired, 
people  injuries  or  material  damages  could  be  caused.  Disconnect  the  power  supply  of  the  unit  before 
carrying out any maintenance operation. 
Make sure that the maintenance areas are accessible. If these areas have to be invaded by the lateral air 
supply and/or return ducts, verify that the design of the ducts allows the access to the fans and that they 
are not a hindrance when replacing the filters.  If that is not possible make sure access is possible from the 
other side.   

All operations shall be carried out in accordance with the local safety regulations. 

 
Repairing Operations 

 

 

The reparations shall always and exclusively be completed by trained personnel previously authorized by 
the manufacturer and only original spares shall be used. The safety devices of the unit may be damaged 
in case of non-compliance with these warnings. 

 
Modifications 
 

The  manufacturer  will  not  respond  to  possible  warranty  claims  and  damages  of  the  unit  in  case  of  electrical  and/or 
mechanical modifications. The unauthorized manipulation, reparation or modification of the unit will automatically invalidate 
the warranty.  

 

 

Packaging and Replacement of Equipment 
 

 

The material of the package (plastic bags, insulating materials, nails, etc.) is a potential source of danger. 
Consequently, it should be kept out of the reach of children and properly recycled according to the valid 
local safety regulations.  
Do  not  mix  this  product  with  household  waste  at  the  end of  its  life.  Due to  the  refrigerant,  oil  and  other 
components  contained  in  this  product,  it  must  be  dismantled  by  professional  installers.  All  the 
waste, depending  on  its nature shall  be  sent  to recycling,  composting  or  treatment  plants,  or  to  an 
authorized management agency in accordance with the current local legislations. 

 
 

Refrigerant 
 

This product is hermetically sealed and its operation depends on the use of R-410A which is a HFC fluorinated greenhouse 
gas. 
 
 

REGULATIONS AND CERTIFICATIONS 

 
ISO  9001  CERTIFICATION: 

HIPLUS  AIRE  ACONDICIONADO  S.L.,  by  endeavouring  to  always  gain  the  maximum 

satisfaction from their customers, obtained the ISO 9001: Quality System for its design and production activities. That result 
shows  our continuous  determination  to improve  quality  and  the  reliability  of  all  our  products.  Our  commercial  activities, 
design, raw materials, production processes and after-sales service represent the means to reach our goal.  
 

CE MARKING

: Our products are CE marked according to the essential requirements of the applicable EC directives and 

their last modifications and comply with the national legislation of each country.  
 
 
 
 
 

 

Содержание CLVBA-CLVA 401

Страница 1: ...401_208095_200801_EN INDOOR UNITS FOR DUCT INSTALLATIONS AIR AIR CLVBA CLVA ECCEECHAECHA Cooling Only Heat Pump Model 401 Cooling Capacities 12 1 kW Heating Capacities 12 7 kW INSTALLATION OPERATION MAINTENANCE MANUAL ...

Страница 2: ...oach is based on efficiency flexibility and on practical solutions This has been the hallmark of our product catalogue The versatility of our factory allows us to deliver solutions that can meet any requirement and we endeavour solving any problem that may arise in designing and implementing air conditioning installations From all of us at Hiplus Aire Acondicionado once again thank you very much ...

Страница 3: ...N 8 RIGGING 8 STORAGE 8 INSTALLATION 9 INSTALLATION LOCATION 9 UNIT SETTLEMENT 9 SERVICE AREA MM 9 WEIGHT DISTRIBUTION 9 DIMENSIONS 10 DRAINAGE 11 AIR DUCTS 12 DESIGN OF THE REFRIGERANT PIPES 12 ELECTRICAL INSTALLATION 12 ELECTRICAL DATA 12 Electrical connections 13 OPERATION 14 BEFORE START UP 14 START UP 14 INDOOR FAN TRANSMISSION ADJUSTMENT 15 OPERATION LIMITS 16 MAINTENANCE 17 CONSERVATION AND...

Страница 4: ...ontinuous improvement in design and performance to which we are committed to gives us the right to modify the specifications of our products without prior notice Electrical Supply Check that the electrical network features comply with the data shown in the data nameplate of the unit Local Safety Regulations Observe and analyse all the possible causes of accidents that may arise in the place or pla...

Страница 5: ...ion or modification of the unit will automatically invalidate the warranty Packaging and Replacement of Equipment The material of the package plastic bags insulating materials nails etc is a potential source of danger Consequently it should be kept out of the reach of children and properly recycled according to the valid local safety regulations Do not mix this product with household waste at the ...

Страница 6: ...ion commissioning and carry out maintenance works Unqualified staff can only make basic tasks such as cleaning and replacement of filters etc Prevent access to children so they cannot play with the appliances In every visit all precautions must be taken into account those recommended in the installation operation and maintenance instructions as well as the ones indicated in labels of the unit Do n...

Страница 7: ... 10 SS Motor power kW 0 55 Voltage V 400 3 N REFRIGERANT Tiype R410A Global Warming Potential GWP 3 2088 Charge 4 1 Return temperature 27 C dry bulb and 19 C humid bulb evaporation temperature 7 C 2 Return temperature 20 C condensation temperature 40 C 3 GWP Global warming potential climatic of 1 kg of greenhouse gas relative to 1 kg of CO2 calculated in terms of 100 year warming potential 4 The c...

Страница 8: ...milar to the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations when it is lifted STORAGE If the equipment is going to be stored before the installation please follow the instructions below in order to avoid damages corrosion or deterioration Move it carefully Do not place the machine in p...

Страница 9: ...talled is able to support its weight in operation Fit shock absorbers throughout the installation to prevent the transmission of noise and vibration Check that the direction of the sound level is not going to disturb anyone UNIT SETTLEMENT Make sure that the unit is correctly levelled The bed frame should have the area and the strength to support the weight of the unit Be sure that after settlemen...

Страница 10: ...AIR AIR INSTALLATION DIMENSIONS Model CLVBA CLVA 401 LEGEND 1 Electrical heater option 2 Supply plenum option 3 Heat water resistance option 4 Coil 5 Fan 6 Fan motor 401 model 7 Fan motor 501 model 8 Air filter 9 Power connexion inlet 10 Gas line 11 Liquid line 12 Drain ...

Страница 11: ...on depending on the line length and general building configuration The drainage line should inclined a minimum 2 for proper water evacuation When drain line is exposed to temperatures below 0 degrees it is necessary to cover with thermal insulation or electrical heating wire to avoid water freezing and tube damages It is convenient to install the water drain trap with proper dimensions see diagram...

Страница 12: ...e instructions stated in the condenstion unit ELECTRICAL INSTALLATION Unit power supply should be within 10 of volts indicated on the unit nameplate Damage caused by the start up of the unit in an incorrect voltage line is not covered by Hitecsa s warranty When making electrical connections always use the unit wiring diagram The line protection elements have to be placed by the installer according...

Страница 13: ...APORATION UNITS AIR AIR INSTALLATION ELECTRICAL INSTALLATION Electrical connections For further information please refer to the user manual and to the electrical diagram Legend 1 Ground 2 Power supply 3 Magnetothermal circuit breaker D curve differential ...

Страница 14: ...lied with any other voltage than that the indicated on the serial plate The power supply to the unit must be within 10 of the voltage indicated on the serial plate Check the correct rotation direction of the fans The installer must place line protection elements in accordance with current legislation Wiring of electrical connections must be protected by a tube or other cable conduits Make sure if ...

Страница 15: ...et screws 4 Place the belt in the pulley cannel The closure of opening of the pulley could void the size of the prior belt In this case replace it for other belt of the same profile and with the appropriate length 5 Tighten the belt by using tensor screw or sliding the motor depending on the case Align fan and motor pulleys 1 Loose fan pulley set screws 2 Slide fan pulley along the shaft and align...

Страница 16: ...nal value it means that the unit air flow is too low MODELS Nominal Pulley Correa Open kW A Fixed Variable 401 0 55 1 52 150 E20 1A 75 100 E19 1A A 40 1 OPERATION LIMITS AMBIENT AIR TEMPERATURE DRY TEMP HUMID TEMP COOLING CYCLE ºC ºC Standard conditions 27 19 Minimum conditions 21 15 Maximum conditions 32 21 AMBIENT AIR TEMPERATURE DRY TEMP DRY TEMP HEATING CYCLE ºC ºC Standard conditions 20 Minim...

Страница 17: ...t be based on the working conditions to avoid the accumulation of dirt in propellers turbines motors and grids that could entail risks and shorten its life Be very careful not to unbalance the propeller or the turbine in cleaning operations Must observe the current safety legislations of each country in all maintenance and repairing works Motors and fans do not need any additional lubrication Tran...

Страница 18: ...18 IOM_CLVBA CLVA_401_208095_200801_EN CLVBA CLVA EVAPORATION UNITS AIR AIR Subject to modifications without prior notice ...