EVAPORATION UNITS AIR-AIR
OPERATION
FAN TRANSMISSION ADJUSTMENT
Adjust transmission in such a way that the indoor motor consumption comes to its normal value.
If consumption is below nominal value it means that the unit air flow is too low.
MODELS
Nominal
Pulley
Correa
Open
kW
A
Fixed
Variable
401
0,55
1,52
150 E20 1A
75/100 E19 1A
A-40
1
OPERATION LIMITS
AMBIENT AIR TEMPERATURE
DRY TEMP.
HUMID TEMP.
COOLING CYCLE
ºC
ºC
Standard conditions
27
19
Minimum conditions
21
15
Maximum conditions
32
21
AMBIENT AIR TEMPERATURE
DRY TEMP.
DRY TEMP.
HEATING CYCLE
ºC
ºC
Standard conditions
20
–
Minimum conditions
20
–
Maximum conditions
26
–