EVAPORATION UNITS AIR-AIR
DRAINAGE
The indoor unit drainage (condensate w
ater) has a 3/4” MPT connection.
Condensate drain pipe diameter should be equal or larger than the unit drain connection depending on the line length
and general building configuration.
The drainage line should inclined a minimum 2% for proper water evacuation.
When drain line is exposed to temperatures below 0 degrees, it is necessary to cover with thermal insulation or electrical
heating wire to avoid water freezing and tube damages.
It is convenient to install the water drain trap with proper dimensions (see diagram).
Recommended water drain trap
measures