![Hitecsa ACVIBA HE 35i Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/hitecsa/acviba-he-35i/acviba-he-35i_installation-operation-and-maintenance-manual_2140071016.webp)
16
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
TRANSPORT
STORAGE
If the equipment is going to be stored before the installation, please follow the following instructions in order to avoid
damages, corrosion or deterioration:
Move it carefully.
Do not place the machine in places exposed to ambient temperatures above 50ºC and preferably keep the unit away
from direct sunlight.
The sun radiation may cause a very high temperature increase that can make the refrigerant pressure reach such high
levels that the security valves would be activated.
1. Moreover, when temperatures decrease water condensation may occur inside the machine or between the machine
and the plastic wrap.
Avoid placing objects on top of the unit (unless this is permitted according to the drawings or the overlap diagrams
indicated on the packaging, etc. Follow these indications).
In case of prolonged storage before installation avoid the penetration of water, dust and objects in general caused by
invasion or biological, meteorological and/or human impacts.
Minimum storage temperature: -10ºC.
2. If some components contain water, it is compulsory to empty them or to add an antifreeze solution to make sure that
the freezing point will always be lower than the ambient temperature.
Maximum relative humidity: 90%.
The warranty will not cover any damage caused frozen water.
WARNING