25
IOM_UMXCBA-UMXCA_801.1a4502.2_208027_200201_EN
UMXCBA/UMXCA
CONDENSER UNITS WITH
COMPRESSOR AND AXIAL FAN
OPERATION
pGD1 or Mini PGD THERMOSTAT
Time Schedule
Important: In case of having a TH-TUNE thermostat, you will previously have to deactivate it in order to
make any modification on the pGD1 safely.
The start-stop from keyboard will prevail over any time schedule that it is activated.
Note: In order to accede to these menus with other controllers that are not µPC or PCO3, you will have to
install the PCO100CLK0 model optional card and have enabled the clock function from the user menu
(password 1996).
-
Clock adjust in pGD1 models as standard (HIT005)
1. Press
“
Prog
”
key
2. Select menu 5. TIME SCHEDULE
3. Modify Hour, Date y Day
-
Time schedule pGD1 models as standard (HIT005)
You will have 4 types of start in time schedule, and when the time schedule is ON the screen will display
the word PHASE:
A.
Manual type
: by selecting this type of start the unit will be ON or OFF without taking into account the
internal clock.
Example:
The machine will stay stopped until the type
of start is changed.
B.
ON/OFF type:
week schedule. You can define between 3 different schedules for each day of the week
with until three operation time slots on each one.
In the menu 5, select the “Schedule ON-OFF” start type.
The three programs are defined afterwards:
Example: From Monday to Thursday the num1 program activates, which starts up
the machine at 6:30 and stops it at 11:00, starts again from 11:30 to 13:30 and
from 15:00 to 19:00. On Friday the number 3 program activates, which starts up
the machine from 7:00 to 15:00 and Saturdays and Sundays no program is
activated, the machine remains stopped.
Содержание 1602.2