UMXCBA/UMXCA

 

CONDENSER UNITS WITH 
COMPRESSOR AND AXIAL FAN

 

 

MAINTENANCE 

 

Transmission belts: 

Check the status and tension of the transmission belt, at least twice the first month of 

operation, and then every 1000 hours of operation. 
 

Drainage system

: Verify the condition and the correct operation of the drainage tray and drain trap. It is 

necessary to clean the condensate trays after the first day of operation. Then, clean them at least once a 
year. Take into account the meteorological conditions, e.g. in areas where falling leaves or the flight of 
seeds may obstruct the drain trap, it will also be necessary to clean them at mid and late spring and 
autumn. The dates are approximate and will depend on the blooming, falling leaves, seeds, etc. of the 
plants of the zone or the human activity or any other cause. 

(Check the access to the condensates trays) 

 

Air filters: 

Clean the filters after the first operating hours to remove possible light materials such as pieces of 

paper or polystyrene, etc. that may have been dragged through air circulation. Clean again every 3 months (or 
more often depending on operation). The filters can be cleaned with soapy water. Then rinse them with clean 
water and let dry. If necessary replace the filters before they are in poor conditions (refer to the current legislation, 
EN 779, UNE-

EN 13053…). 

 

COMPRESSOR LUBRICANT 

 
R-410A refrigerant compressors use synthetic polyol ester oil. Each compressor manufacturer has a 
specific oil for their products.  
The compressor or system should not remain open to atmosphere for more than 15 minutes. 
Synthetic ester-type lubricants (POE, Polyol Ester) with a high solubility level with R-410A are used. These 
types of oil are very hygroscopic and shall be handled with more care than the conventional oils. 
Moreover, when these synthetic oils are mixed with minerals (MO) or alkylbenzenes (AB), they deteriorate 
causing capillary blockage or failure in the compressor.  
 

DO NOT MIX THEM UNDER ANY CIRCUMSTANCES.

 

 

 

 

REFRIGERANT CHARGE 

 

 

 

Should it be necessary to add or recover refrigerant use a digital scale that is suitably reinforced and 
prepared to withstand the handling of the refrigerant bottle. 

 

 

The charge must be made in the LIQUID condition. 

 

 

The inlet of liquid refrigerant R-410A in the empty tubes causes temperatures below 0ºC until the internal 
pressure reaches 7 bars. 

 

 

 

 

Leaks should be repaired immediately. 

 

Never overcharge the system.  

 

Never use the compressor as a vacuum pump.  

 

If leakage symptoms appear during operation, proceed to a leak test.  

 

A HCF detector is necessary in case of small leaks.  

 

If a gas leak is detected proceed to removing and recuperating the entire refrigerant charge. Pressurize 
the  system  with  dry  nitrogen.  If  no  leak  is  detected  proceed  to  vacuuming  the  system  and  refill  with 
refrigerant. 

Do not reintroduce the used refrigerant, send it to an authorized recycling plant. 

Never use oxygen to pressurize the system or purge lines for leak test. Oxygen reacts violently 

with oil which may entail an explosion that could lead to damages, personal injury or event 

death.

 

WARNING! 

Should it be necessary to make brazing operation proceed previously to filling the circuit with 

dry nitrogen. Burning refrigerant produces toxic gas emissions. 

WARNING! 

Содержание 1602.2

Страница 1: ...2 2402 2 3002 2 3502 2 4002 2 4502 2 Cooling capacity from 25 9 kW to 134 7 kW Heating capacity from 27 3 kW to 142 4 kW CONDENSER UNITS WITH COMPRESSOR AND AXIAL FAN INSTALLATION OPERATION MAINTENAN...

Страница 2: ...ars Our approach is based on efficiency flexibility and on practical solutions This has been the hallmark of our product catalogue The versatility of our factory allows us to deliver solutions that ca...

Страница 3: ...S 12 Refrigerant circuit 12 Discharge lines 12 LINE DESIGN 12 REFRIGERANT LINES 13 LINE DRAWING 13 Additional load in the interconnection pipes 14 REFRIGERATION CONNECTIONS 15 Guidelines for the corre...

Страница 4: ...erature adjustment 24 System operating modes change 24 Time Schedule 25 Local Network 28 Alarms 29 MAINTENANCE 31 CONSERVATION AND CLEANING 31 COMPRESSOR LUBRICANT 32 REFRIGERANT CHARGE 32 DIMENSIONS...

Страница 5: ...the Data The continuous improvement in design and performance to which we are committed to gives us the right to modify the specifications of our products without prior notice Electrical Supply Check...

Страница 6: ...d manipulation reparation or modification of the unit will automatically invalidate the warranty Packaging and Replacement of Equipment The material of the package plastic bags insulating materials na...

Страница 7: ...carry out basic tasks only such as cleaning and replacement of filters or filter cleaning excluding the refrigerant filters etc Prevent access to children to avoid that they play with the equipment Fo...

Страница 8: ...1 5 8 Gas line diameter circuit 1 1 1 8 Liquid line diameter circuit 2 Gas line diameter circuit 2 FAN Type Outdoor Axial Rotor Nominal air flow m3 h 17700 17700 19700 19700 Available static pressure...

Страница 9: ...er circuit 1 5 8 Gas line diameter circuit 1 1 1 8 Liquid line diameter circuit 2 5 8 Gas line diameter circuit 2 1 1 8 FAN Type Outdoor Axial Rotor Nominal air flow m3 h 35400 35400 39400 39400 Avail...

Страница 10: ...circuit 1 7 8 Gas line diameter circuit 1 1 3 8 Liquid line diameter circuit 2 7 8 Gas line diameter circuit 2 1 3 8 FAN Type Outdoor Axial Rotor Nominal air flow m3 h 46400 65900 65900 Available sta...

Страница 11: ...own below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations during the lifting operations STORAGE If the...

Страница 12: ...transmission of noise and vibration Check that the direction of the sound level will not disturb anybody The standard version of this equipment has been designed for installation inside a building wit...

Страница 13: ...qualified technicians An incorrect design may reduce the unit s performance and may be a hindrance when access to the unit for maintenance operations is needed in particular where there is only one po...

Страница 14: ...ne pressure drop The refrigerant circulation speed The refrigerant mass in the system The length of the interconnection pipes please contact Hitecsa for lines longer than 50 meters Discharge lines In...

Страница 15: ...indoor unit is installed at the same level as the outdoor unit raise the suction line to a higher level than the indoor heat exchanger in order to avoid refrigerant return into the compressor during...

Страница 16: ...2 647 22 9 808 28 6 1 3 8 24 853 120 4 3 241 8 5 481 17 1 722 25 6 963 34 1 1204 42 6 1 5 8 34 1219 172 6 1 344 12 2 688 24 4 1033 36 6 1377 48 8 1721 60 9 2 1 8 61 2149 303 10 7 607 21 5 1213 43 0 18...

Страница 17: ...d leave particles inside the pipe Reduce the number of brazing and remember that it should always be of the strong type In compliance with local laws the welder must be an authorized person A bad weld...

Страница 18: ...ding to the current local laws The interconnecting wires shall be protected by a tube or an electrical cable conduit cable tray etc ELECTRICAL DIAGRAM For further details please refer to the electrica...

Страница 19: ...MXCBA UMXCA CONDENSER UNITS WITH COMPRESSOR AND AXIAL FAN INSTALLATION ELECTRICAL DIAGRAM pGD1 or Mini pGD control Connection to pGD1 via 6 wire telephone cable for lines longer than 50m intercalate w...

Страница 20: ...make the connections Make sure that all electrical connections are properly tight The power supply of the unit must comply with the data stated on the serial plate Damage caused by the start up of th...

Страница 21: ...e unit air flow is too low How to change the fan speed 1 Remove the belt Move the motor along its track or loosen the tensor set screw in order to release it 2 Loose the set screws of the motor pulley...

Страница 22: ...t flexibility is calculated in millimeters by dividing S by 40 OPERATION LIMITS OUTDOOR AIR TEMPERATURE Dry temperature COOLING CYCLE C Minimum conditions 20 Maximum conditions 50 HEATING CYCLE C Mini...

Страница 23: ...or negative that shall be added to the value of the probe A value equal to zero will not change the value of the probe Press keys FAN ON OFF and keep them pressed until a password is required Enter pa...

Страница 24: ...rd Auto will disappear from the icon The fan works in a continuous mode Keep the button pressed during 3 seconds minimum until Clock appears if the stated hour is not correct you can change it here tu...

Страница 25: ...3 disconnected Comp 1 discharge Temperature AL05 Alarm probe B5 disconnected Return humidity AL06 Alarm probe B6 disconnected Return humidity AL07 Alarm probe B7 disconnected Outdoor humidity AL11 Ala...

Страница 26: ...submenu help is shown on the main screen UP KEY Scrolling through the menus or modification of the values of the regulation parameters ENTER KEY Confirmation of the introduced values DOWN KEY Scrollin...

Страница 27: ...hedule pGD1 models as standard HIT005 You will have 4 types of start in time schedule and when the time schedule is ON the screen will display the word PHASE A Manual type by selecting this type of st...

Страница 28: ...from 6 30 to 11 00 etc D ON OFF schedule type with SET limit of ON This option makes the start stop as option B ON OFF schedule including a safety start up of the unit out of the schedule when the tem...

Страница 29: ...2 00 a m Example DST of 60 min Enabled from the first Monday of February at 10 00 goes off at 11 00 until the last Sunday of October at 3 00 goes back at 2 00 The pGD1 is an option HITSAA01 Various ty...

Страница 30: ...5 Press the three buttons until the next image appears again on the screen return the display address setting value to 32 Press Enter to confirm 6 Set I O Board address to the desired value that we e...

Страница 31: ...ALARM MESSAGES pGD1 Optional HITSAA01 Message in Display Type Alarms Clock card error or not connected Warning Alarms Probe B01 broken or disconnected Warning Alarms ThTune offline Alarm Alarms ThTune...

Страница 32: ...m General Alarm of the Burner Alarm Severe Damaged Memory indication Warning Missing Clock or not working Alarm Maintenance of the unit Only indication Warning Alarms Severe Return Temperature Probe B...

Страница 33: ...opped and control that nobody may start it during the intervention A regular inspection of the unit is required to avoid dirt accumulation in propellers turbines motors and grids that could entail ris...

Страница 34: ...or system should not remain open to atmosphere for more than 15 minutes Synthetic ester type lubricants POE Polyol Ester with a high solubility level with R 410A are used These types of oil are very h...

Страница 35: ...7_200201_EN UMXCBA UMXCA CONDENSER UNITS WITH COMPRESSOR AND AXIAL FAN DIMENSIONS UMXCBA UMXCA 801 1 1001 1 1201 1 1501 1 LEGEND 1 Liquid pipes connection 2 Gas pipes connection 3 Electrical box 4 Mai...

Страница 36: ...2 3002 2 CENTRE OF GRAVITY X Y Z UMXBCA 1602 2 684 1056 635 UMXCBA 2002 2 680 1057 670 UMXCBA 2402 2 680 1058 665 UMXCBA 3002 2 685 1058 672 LEGEND 1 Lower inlet for electrical power 2 Electrical box...

Страница 37: ...S WITH COMPRESSOR AND AXIAL FAN DIMENSIONS UMXCBA UMXCA 3502 2 4002 2 4502 2 LEGEND 6 Lower inlet for electrical power 7 Electrical box 8 Main switch 9 Standard inlet for electrical power 10 Connectio...

Страница 38: ...of high temperatures flames burning surfaces and excess humidity Hazardous Reactions Contact with certain red hot metals may result in exothermic or explosive reactions and yield toxic and or corrosi...

Страница 39: ...Subject to modifications without prior notice...

Отзывы: