ROOF TOP UNITS 

– AXIAL FAN  

 
 
 
 
 

RMXCA/RMXCBA

 

VRC MODULE TECHNICAL FEATURES 

MODULE WITH CENTRIFUGAL RETURN FAN 

 

  

 KUBIC series 

1402.2 

1602.2 

2002.2 

2402.2 

3002.2 

3502.2 

4002.2 

4502.2 

  

CAPACITIES 

Cooling capacities 

(1)

 

kW 

48,2 

54,9 

68,0 

82,8 

91,0 

118,7 

131,1 

141,2 

Power input 

(3)

 

kW 

17,2 

21,4 

23,2 

30,8 

36,5 

43,3 

49,3 

55,7 

EER coefficient 

kW/ kW 

2,80 

2,56 

2,93 

2,69 

2,49 

2,74 

2,66 

2,53 

Heating capacities 

 (2)

 

kW 

48,4 

56,7 

67,3 

83,2 

93,3 

121,2 

137,3 

150,4 

Power input 

(3)

 

kW 

14,9 

18,8 

19,9 

27,0 

31,5 

39,4 

46,5 

51,9 

COP coefficient 

kW/ kW 

3,24 

3,01 

3,38 

3,09 

2,96 

3,08 

2,95 

2,90 

  

REFRIGERANT 

Type 

  

R-410A 

PCA 

(4)

 

  

2088 

Load 

Kg 

12,5 

13,2 

14,1 

15,4 

16,2 

31,0 

32,0 

33,0 

  

COMPRESSOR 

Type 

  

Scroll 

Quantity 

  

Number of refrigerant circuits 

  

Number of stages  

(5)

 

  

Oil type 

  

Danfoss POE 160 SZ 

  

OUTDOOR FAN  CIRCUIT  

Type 

Un 

Axial Rotor Exterior 

Quantity 

Un 

Nominal air flow  

m

3

/h 

31724 

31724 

39332 

39332 

39332 

39332 

60088 

60088 

Available static pressure 

Pa 

Diameter 

mm 

710 

800 

710 

Power 

kW 

1,25 / 0,97 

1,9 / 1,2 

1,25 / 0,97 

Speed 

rpm 

950/825 

890/690 

950/825 

  

INDOOR CIRCUIT 

Nominal air flow 

m

3

/h 

9000 

10200 

11500 

14000 

15500 

21000 

23000 

25000 

Available static pressure 

Pa 

100 

100 

125 

125 

125 

150 

150 

150 

Quantity / Size 

--- 

15/15 

2 x 15/11 

2 x 18/18 

Power 

kW 

1,5 

2,2 

2,2 

5,5 

5,5 

5,5 

Speed 

rpm 

616 

677 

712 

802 

860 

642 

673 

860 

Condensates drainage 

Ø 

Junction 3/4" 

  

RETURN CIRCUIT 

Nominal air flow 

m

3

/h 

9000 

10200 

11500 

14000 

15500 

21000 

23000 

25000 

Available static pressure 

Pa 

75 

75 

100 

100 

100 

100 

100 

100 

Quantity / Size 

--- 

15/15 

2 x 15/11 

2 x 18/18 

Power 

kW 

1,5 

2,2 

2,2 

5,5 

Speed 

rpm 

5,75 

604 

602 

686 

742 

568 

603 

637 

Condensates removal 

Ø 

Junction 3/4" 

  

ELECTRICAL FEATURES 

Power supply 

  

400V -3N 50Hz 

Max. power input 

kW 

23,7 

28,1 

32,3 

37,2 

44,0 

59,0 

66,8 

73,8 

Start-up current 

76,0 

95,0 

102,3 

208,4 

220,1 

273,5 

310,7 

346,7 

  

DIMENSIONS 

Length 

mm 

3988 

5845 

Width 

mm 

2219 

2219 

Height 

mm 

1240 

1900 

  

TRANSPORT 

Weight 

Kg 

1233 

1265 

1347 

1376 

1442 

2238 

2380 

2405 

Shipping 

Un x 20”/40”/40”HQ 

1 / 3 / 6 

 
All data measured for a flow renovation at 25 %. 

(1) Nominal cooling capacity: Outdoor temperature: 35 ºC. Dry indoor temperature: 19 ºC. 
(2) Nominal heating capacity: Wet outdoor temperature: 6 ºC. Indoor temperature: 20 ºC. 
(3) Motor fans and compressors power input in previous conditions. 
(4) Global warming potential of one kg of fluorinated gas of greenhouse effect relative to one kilogram of carbon dioxide over a period of 100 years. 
(5) The number of stages is increased by one with free-cooling (FC). 

Содержание 1402.2

Страница 1: ...eration and Maintenance Manual Cooling Only Heat Pump RMXCA RMXCBA ROOF TOP UNITS AXIAL FAN Models 1402 2 1602 2 2002 2 2402 2 3002 2 3502 2 4002 2 4502 2 Cooling Capacities from 46 1 to 178 4 KW Heat...

Страница 2: ...ears Our approach is based on efficiency adaptability usability and practical solutions This has been the hallmark of our product catalogue The versatility of our factory allows us to contribute solut...

Страница 3: ...UBRICANT 16 STD TECHNICAL FEATURES 17 RCF MODULE TECHNICAL FEATURES 18 VRC MODULE TECHNICAL FEATURES 19 DIMENSIONS 20 MODELS 1402 2 1602 2 STD 20 MODELS 2002 2 3002 2 STD 21 MODELS 3502 2 STD 22 MODEL...

Страница 4: ...of children Recycle packaging materials in accordance with local law Units must be used only for the purpose for which they were designed The manufacturer is not liable in the case of applications ot...

Страница 5: ...y accessory recommended for any particular task For brazing operations use a quenching cloth and keep a fire extinguisher at a close distance When repairing the unit use only original spare parts and...

Страница 6: ...y Raise and set down the equipment carefully During the transport never tip or roll the unit more than 15 degrees To lift the unit a crane can be used Suggestions for the transport company are found b...

Страница 7: ...se a location free of dust and foreign matter which can clog or damage condenser coil Consult and respect all regulations concerning installation of air conditioning systems UNIT SETTLEMENT Kg Ensure...

Страница 8: ...8 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODEL 3502 2 STD MODELS 4002 2 4502 2 STD...

Страница 9: ...9 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODELS 1402 2 3002 2 RCF MODEL 3502 2 RCF...

Страница 10: ...10 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODELS 4002 2 4502 2 RCF MODELS 1402 2 3002 2 VRC...

Страница 11: ...11 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODEL 3502 2 VRC MODELS 4002 2 4502 2 VRC...

Страница 12: ...tions 1 Power Supply 400V 3N 50Hz 2 Disconnect Switch 3 Control POWER SUPPLY 230 v AC 3 2 BELDEN TYPE BRAIDDING AND SHIELDED 1 L N T Ensure that all electrical connections are correct Ensure that all...

Страница 13: ...titude of 1500 m For other conditions please consult us For lower temperatures it is necessary to use the condensation control supplied as optional The electrical power supply to the unit should agree...

Страница 14: ...ctions The indoor drain of condensate water has an MPT 3 4 pipe connection The outdoor recovery drain of condensate water has MPT 3 4 pipe connection Condensate evacuation line diameter should be equa...

Страница 15: ...ption reaches its nominal value If consumption is below the nominal value then the airflow in the unit is too low To change fan speed 1 In order to remove belt move motor along its track 2 Loosen pull...

Страница 16: ...to atmosphere more than 15 minutes Compared to the mineral oil used with R22 compressors polyoilester lubricants absorb more than 100 times more the moisture Mineral oils or alkylbenzene type synthet...

Страница 17: ...CIRCUIT Nominal air flow m 3 h 9000 10200 11500 14000 15500 21000 23000 25000 Available static pressure Pa 100 125 150 Quantity Size 15 15 2 x 15 11 2 x 18 18 Power kW 1 5 2 2 2 2 4 4 4 5 5 5 5 Speed...

Страница 18: ...0 21000 23000 25000 Static pressure available Pa 100 100 125 125 125 150 150 150 Quantity Size 15 15 2 x 15 11 2 x 18 18 Power kW 1 5 2 2 2 2 4 4 5 5 5 5 7 5 Speed rpm 649 726 712 802 860 716 756 798...

Страница 19: ...00 Available static pressure Pa 100 100 125 125 125 150 150 150 Quantity Size 15 15 2 x 15 11 2 x 18 18 Power kW 1 5 2 2 2 2 4 5 5 4 5 5 5 5 Speed rpm 616 677 712 802 860 642 673 860 Condensates drain...

Страница 20: ...198 182 119 1602 2 199 138 119 204 196 119 CENTRE OF GRAVITY mm KUBIC X Y Z 1402 2 1267 1147 604 1602 2 1269 1148 604 LEGEND Standard air supply Optional air supply Standard air return Optional air re...

Страница 21: ...ard Main power switch Electricity supply Condensate drainage 3 4 Anchorage silent block M12 Mouth profile 25 mm Equipment chassis width 130mm WEIGHT DISTRIBUTION kg KUBIC R1 R2 R3 R4 R5 R6 2002 2 203...

Страница 22: ...air return Optional air return Condensates drainage 3 4 Power supply Electrical panel board Main power switch Anchorage silent block M12 Mouth profile 25 mm Equipment chassis width 130mm WEIGHT DISTR...

Страница 23: ...4502 2 401 337 210 309 254 210 CENTRE OF GRAVITY mm KUBIC X Y Z 4002 2 1718 1153 952 4502 2 1709 1150 947 LEGEND Standard air supply Optional air supply Standard air return Optional air return Condens...

Страница 24: ...urn Optional air return Electrical panel board Main power switch Power supply Condensate drainage 3 4 Condensate drainage 3 4 Air renewal damper WEIGHT DISTRIBUTION kg KUBIC R1 R2 R3 R4 R5 R6 R7 R8 14...

Страница 25: ...402 2 210 153 147 175 213 213 151 183 3002 2 212 158 156 193 215 238 151 208 CENTRE OF GRAVITY mm KUBIC X Y Z 2002 2 1941 1122 578 2402 2 1941 1124 578 3002 2 1912 1130 577 LEGEND Standard air supply...

Страница 26: ...ir supply Standard air return Optional air return Electrical panel board Main power switch Power supply Condensate drainage 3 4 Condensate drainage 3 4 Air renewal damper WEIGHT DISTRIBUTION kg KUBIC...

Страница 27: ...urn Optional air return Condensate drainage 3 4 Condensate drainage 3 4 Power supply Electrical panel board Main power switch Air renewal damper WEIGHT DISTRIBUTION kg KUBIC R1 R2 R3 R4 R5 R6 R7 R8 40...

Страница 28: ...3 142 128 115 198 182 139 136 1602 2 199 145 130 115 205 187 143 141 CENTRE OF GRAVITY mm KUBIC X Y Z 1402 2 1898 1149 574 1602 2 1894 1147 574 LEGEND Standard air supply Optional air supply Standard...

Страница 29: ...2402 2 210 153 137 130 213 213 169 151 3002 2 212 158 137 130 215 238 184 168 CENTRE OF GRAVITY mm KUBIC X Y Z 2002 2 1889 1168 584 2402 2 1882 1171 584 3002 2 1868 1177 583 LEGEND Standard air supply...

Страница 30: ...7 R8 3502 2 387 331 304 200 289 283 239 205 CENTRE OF GRAVITY mm KUBIC X Y Z 3502 2 2624 1145 867 LEGEND Standard air supply Optional air supply Standard air return Optional air return Condensate drai...

Страница 31: ...0 304 312 239 205 4502 2 401 393 346 309 312 312 239 205 CENTRE OF GRAVITY mm KUBIC X Y Z 4002 2 2587 1159 896 4502 2 2592 1164 898 LEGEND Standard air supply Optional air supply Standard air return O...

Страница 32: ...r correct installation of the accessory UPPER RAIN HOOD LOWER RAIN HOOD POSITIONING OF THE RAIN HOODS The correct installation of the rain hood accessory is very important to guarantee the proper perf...

Страница 33: ...ction 2 Place the inclined rain hood at the lower window Air renewal DIMESIONS 1402 3002 In case the rain hoods were placed upside down the inclined wall would push the outlet air downwards and this c...

Страница 34: ...34 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA DIMENSIONS 3502 4502...

Страница 35: ...ear during operation it s necessary to carry out a leak test Leak detectors usually employed with CFC and HCFC cannot be used with R410A due to chlorine in its composition A leak detector for R134a ma...

Страница 36: ...adings and record them on the maintenance form Electrical circuit Make sure that all electrical cables are properly tightened Be sure that there are no faulty terminals contactors etc Take the measure...

Страница 37: ...nger of suffocation due to the reduction of oxygen content in the atmosphere Remove patient to fresh air and keep warm and at rest Administer oxygen if necessary Apply artificial respiration if the pa...

Страница 38: ...Wear overalls impervious gloves and eye face protection How to act in case of spill accidental release Make sure to wear protective clothing and breathing apparatus If not dangerous isolate the sourc...

Страница 39: ...Rights reserved subject to change without notice HIPLUS AIRE ACONDICIONADO S L Masia Torrents 2 Tel 34 93 893 49 12 Fax 34 93 893 96 15 08800 Vilanova i la Geltr Barcelona Spain www hitecsa com...

Отзывы: