17
07.16 207477 Rev.108
ROOF TOP UNITS
– AXIAL FAN
RMXCA/RMXCBA
STD TECHNICAL FEATURES
KUBIC series
1402.2
1602.2
2002.2
2402.2
3002.2
3502.2
4002.2 4502.2
CAPACITIES
Cooling capacities
(1)
kW
46,1
52,4
65,1
79,1
86,9
113,6
125,3
134,8
Power Input
(3)
kW
15,5
19,2
21,2
27,7
32,7
39,5
44,4
49,9
EER coefficient
kW/ kW
2,97
2,73
3,07
2,86
2,66
2,88
2,82
2,70
Heating capacities
(2)
kW
46,8
53,9
66,1
80,4
88,7
119,1
132,7
143,0
Power Input
(3)
kW
13,3
16,6
18,0
24,0
27,8
35,6
41,4
45,8
COP coeficient
kW/ kW
3,52
3,25
3,67
3,35
3,19
3,35
3,21
3,12
REFRIGERANT
Type
R-410A
PCA
(4)
2088
Load
Kg
12,5
13,2
14
15,6
16
31
32
33
COMPRESSOR
Type
Scroll
Quantitty
2
Number of refrigerant circuits
2
Number of stages
(5)
2
Oil type
Danfoss POE 160 SZ
INDOOR FAN
CIRCUIT
Type
Un
Outdoor Axial Rotor Exterior
Quantity
Un
2
4
Nominal air flow
m
3
/h
31724
39332
46556
60088
Available static pressure
Pa
0
Diameter
mm
710
800
710
Power
kW
1,25/0,97
1,9/1,2
1,25/0,97
Speed
rpm
950/825
890/690
950/825
INDOOR CIRCUIT
Nominal air flow
m
3
/h
9000
10200
11500
14000
15500
21000
23000
25000
Available static pressure
Pa
100
125
150
Quantity / Size
---
15/15
2 x 15/11
2 x 18/18
Power
kW
1,5
2,2
2,2
4
4
4
5,5
5,5
Speed
rpm
616
677
712
802
860
642
673
707
Condensates drainage
Ø
Junction 3/4"
ELECTRICALS CAHRACTERISTICS
Power supply
400V -3N 50Hz
Max. power input
kW
22,6
26,7
30,6
34,4
40,4
56,3
63,5
69,7
Start-up current
A
72,8
90,1
96,9
192,5
202,1
261,2
295,1
327,2
DIMENSIONS
Length
mm
2886
3900
Width
mm
2219
2219
Height
mm
1240
1900
TRANSPORT
Weight
Kg
944
975
1023
1043
1072
1594
1704
1721
Shipping
Un x 20”/40”/40”HQ
2 / 4 / 8
(1) Calculated according to the standard UNE-EN-14511, for indoor temperature conditions of 27ºC, 50% HR and 35ºC outdoor temperature.
(2) Calculated according to the standard UNE-EN-14511, for indoor temperature conditions of 20ºC and 6ºC BH outdoor temperature.
(3) Total power input by compressor and motor fans in normal conditions, calculated according to the standard UNE-EN-14511.
(4) Climatic warming potential of one kg of fluorinated greenhouse gas in relation to a kg of carbon dioxide over a period of 100 years.
(5) The number of stages is increased by one with free-cooling (FC)
Содержание 1402.2
Страница 8: ...8 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODEL 3502 2 STD MODELS 4002 2 4502 2 STD...
Страница 9: ...9 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODELS 1402 2 3002 2 RCF MODEL 3502 2 RCF...
Страница 10: ...10 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODELS 4002 2 4502 2 RCF MODELS 1402 2 3002 2 VRC...
Страница 11: ...11 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA MODEL 3502 2 VRC MODELS 4002 2 4502 2 VRC...
Страница 34: ...34 07 16 207477 Rev 108 ROOF TOP UNITS AXIAL FAN RMXCA RMXCBA DIMENSIONS 3502 4502...