93
PMML0600 rev.0 - 06/2022
6
SETTING OF DIP SWIT
CHES AND R
SW SWIT
CHES
ELEC
TRICAL AND C
ONTROL SETTINGS
6.2.2.5 DSW5
◆
Additional setting 3
DSW5
RASM-(V)RW(1)E
RASM-(V)R(1)E
HWM-WE
HWD-WE-220S(-K)
Factory setting
4
3
2
1
4
3
2
1
Outdoor unit sensor for circuits 1 and 2.
Not applicable
4
3
2
1
Outdoor unit sensor for circuit 1; Auxiliary sensor for
circuit 2.
Not applicable
4
3
2
1
Auxiliary sensor for circuit 1; Outdoor unit sensor for
circuit 2.
Not applicable
4
3
2
1
Auxiliary sensor instead of outdoor unit sensor for both
circuits.
Not applicable
4
3
2
1
Use the maximum temperature value between Two3
(boiler / heater thermistor) and Two (water outlet
thermistor) for water control
Not applicable
4
3
2
1
6.2.2.6 DSW6 (only if available)
◆
Not used
DSW6
RASM-(V)R(W)(1)E
HWM-WE
HWD-WE-220S(-K)
Factory setting (do not change)
2
1