5.7 Water piping
5.7.1 Water piping length
Consider the following guidelines when designing the water circuit.
Item
YUTAKI HYDROSPLIT R32
YUTAKI H
YUTAKI H Combi
Maximum water piping length between indoor unit and DHW tank
10 m
-
Maximum water piping length between indoor unit and 3-way valve
3 m
-
Maximum water piping length between 3-way valve and DHW tank
10 m
-
Minimum water piping length between YUTAKI Hydrosplit and YUTAKI H or
YUTAKI H Combi
5 m
5 m
Item
YUTAKI M R32
Maximum water piping length between indoor unit and DHW tank
10 m
Maximum water piping length between 3-way valve and DHW tank
10 m
Maximum total piping combination
10 m
5.7.2 Water piping size
◆
Piping location
The unit is factory supplied with two unions to be connected to the water inlet/outlet pipe. Refer
to the next figure detailing the location of the water pipes location.
Water inlet
Water outlet
RASM-(2/3)VRE