Appendix
E:
Power distribution units for Hitachi
Universal V2B Rack
The Universal V2B Rack is equipped with specific power distribution units (PDU) for
Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the racked
system in a single-phase or three-phase configuration.
Caution:
■
Before installing third-party devices into the rack, check the electrical
current draw of each device. Verify the electrical specifications and
allowable current load on each PDU before plugging the device into the
PDU.
■
Balance the electrical current load between available PDUs.
Americas single-phase PDU 1P30A-8C13-3C19UL.P
The following figure and table describe the specifications of the PDU.
Figure 1 Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU
1P30A-8C13-3C19UL.P)
Part
Number
Region
Quantity
Power
input per
PDU
Power output
per PDU
Total rack
amperage
available
1P30A-8C1
3-3C19UL.P
Americas
6/rack
3/side
Single
phase
208V, 30A
(24A rated)
60Hz
Delta/wYe:
N/A
8 IEC C13 + 3
IEC C19
sockets
Max allowable
current: 24A
5kVA
72A (15kVA)
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform G700 Hardware Reference Guide
99