Next steps
If
Warning
appears for
BKM Status
and
?
appears for the
Battery
Lifespan Remaining
values of the batteries, resolve the
Warning
for
BKM
Status
so the
?
returns to a numeral value.
Replacing the BKM backup module
Use the following procedure to replace the BKM backup module.
Procedure
1.
Loosen the blue screw that secures the BKM.
2.
Open the lever forward.
3.
Using both hands, hold the body of the BKM, and then pull out and
remove the BKM.
4.
With the lever of the BKM opened forward, insert the new BKM into the
slot.
5.
Push the BKM all the way into the slot.
6.
Close the lever and tighten the blue screw to secure the BKM.
7.
Confirm that the green
STATUS
LED on the BKM is blinking.
8.
In the
BKMS
tab of the maintenance utility, check that the status of the
BKM you replaced is
Normal
.
9.
Log out and close the
Maintenance Utility
window
Replacing a BKMF
The following sections describe how to replace a BKMF backup module.
Replacing a backup module
271
Service Guide for VSP Gx00 and VSP Fx00 Models
Содержание Virtual Storage Platform F400
Страница 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 222: ...222 Replacing a small form factor pluggable SFP Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 395: ...CBSS CBSSD controller Warning labels on the storage system 395 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 396: ...CBSL CBSLD controller 396 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 398: ...CBLM controller CBLH controller 398 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 401: ...Flash module drive tray Warning labels on the storage system 401 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 402: ...Dense intermix drive tray 402 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 410: ...PCIe switch board 410 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 411: ...NAS module Warning labels on the storage system 411 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...