Procedure
1.
In the
Replace Cache Flash Memory
window, click
Restore.
A progress bar shows the replacement status.
2.
When the progress bar goes away and the completion message appears,
click
Close
.
3.
Click the
CFMs
tab in the
Controller Chassis
window.
4.
Verify that the status of the new CFM is
Normal
.
If necessary, click
Refresh
at the top-right of the window to update the
status of the window.
5.
Log out and close the
Maintenance Utility
window.
Checking cache flash memory screws
Procedure
1.
In the
Alert Detail
window of the maintenance utility, click
Close
.
2.
In the left pane, click
Controller Chassis
.
3.
Click the
CFM
tab of the maintenance utility to check the location of the
target CFM.
4.
Click the target CFM, and then click
Replace
.
Maintenance Utility window for CBSS or CBSL
Maintenance Utility window for CBLM or CBLH
256
Replacing cache flash memory
Service Guide for VSP Gx00 and VSP Fx00 Models
Содержание Virtual Storage Platform F400
Страница 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 222: ...222 Replacing a small form factor pluggable SFP Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 395: ...CBSS CBSSD controller Warning labels on the storage system 395 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 396: ...CBSL CBSLD controller 396 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 398: ...CBLM controller CBLH controller 398 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 401: ...Flash module drive tray Warning labels on the storage system 401 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 402: ...Dense intermix drive tray 402 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 410: ...PCIe switch board 410 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 411: ...NAS module Warning labels on the storage system 411 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...