![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 99](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379099.webp)
4 Control system
Printed circuit board for complementary systems
SMGB0137 rev.0 - 05/2021
89
4
4.10.2 Printed circuit board for DX-Interface (PI073)
FUSE
PCB1
PCB2
PCB1 LED indicator
LED1
Red
This LED indicates the transmission
status between the indoor unit and the
remote control.
LED3
Yellow
This LED indicates the transmission
status between the indoor unit and the
outdoor unit.
LED4
Green
PCB power supply
PCB2 LED indicator
LED1
Yellow
H-LINK transmission external
LED2
Green
PCB power supply
LED3
Yellow
H-LINK transmission internal (between
PCBs)
PCB1 Connector indication
PCN1
230V transformer
PCN2
Terminal board 1 (TB1) (19-20) Internal thermostat
for indoor unit fan motor
PCN6
Terminal board 1 (TB1) (11-12) Motor for drain
discharge mechanism
PCN7
Terminal board 1 (TB1) (1-2) and PCB2 power
supply
PCN10
Terminal board 1 (TB1) (13-14)
PCN11
Terminal board 1 (TB1) (15-16)
THM1
Coil inlet thermistor
THM2
Coil outlet thermistor
THM3
Liquid pipe thermistor
THM5
Gas pipe thermistor
CN1
Transformer 12V
CN2
TB2 (19-20) and PCB2
CN11
TB1 (3-8) Expansion valve
CN14
TB2 (15-16) Flow switch
EFR1
Power supply fuse
EF2
PCB fuse
EF3
Fuse for PCN5 connector
PCB2 Connector indication
PCN1
TB1 (1-2) and PCB1
THM1
Optional air temperature sensing
THM2
Optional air temperature sensing
CN1
TB2 (17-18) and PCB1
CN2
TB2 (12-14) Duty V (0~10 V)
CN3
TB2 (1-3) Duty A (1~20 mA)
CN4
TB2 (4-5) CO
2
option ON/OFF
CN5
TB2 (6-8) EC fan motor (Top)
CN6
TB2 (9-11) EC fan motor
EF1
PCB2 fuse
Switch indication
DSW1
Optional functions
DSW2
End resistance
DSW3
Capacity code
DSW4
Unit model code
DSW5,
RSW2
Refrigerant cycle number setting
DSW6,
RSW1
Indoor unit number setting
DSW7
Fuse recovery