![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 94](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379094.webp)
4 Control system
Printed circuit board for RPI-(8.0-20.0)FSN3(P)E(-f) units (PI065-PI005)
SMGB0137 rev.0 - 05/2021
84
4.7 Printed circuit board for RPI-(8.0-20.0)FSN3(P)E(-f) units (PI065-PI005)
CN403
CN404
CN401
CN402
YX2
YX5
YX4
YX3
X2
X5
X4
X3
R
LED indicator
LED1
Red
This LED indicates the transmission
status between the indoor unit and
the remote control.
LED3
Yellow
This LED indicates the transmission
status between the indoor unit and
the outdoor unit.
LED4
Red
PCB power supply
PCB1 Connector indication
PCN1
220 V transformer
PCN2
Internal thermostat for indoor fan motor
PCN3
Fan stoppage alarm signal
PCN6
Drain pump motor (RPI)
PCN7
Terminal board - Power supply
THM1
Air inlet thermistor
THM2
Air outlet thermistor
THM3
Liquid pipe thermistor
THM4
Optional connector (for remote temperature
sensor)
THM5
Gas pipe thermistor
EFR1
Power supply fuse
EF1
Fuse for PCN5 connector
EF4
PCB fuse
CN1
Transformer (20 V)
CN2
Terminal board - H-LINK control circuit and
remote control switch
CN3
Optional input functions
CN7
Optional output functions
CN8
Optional output functions
CN11
Printed circuit board 2 (CN401)
CN17
Printed circuit board 2 (CN404)
CN14
Float switch (RPI)
PCB2 Connector indication
CN401
Printed circuit board 1 (CN11)
CN404
Printed circuit board 1 (CN17)
CN402
Expansion valve control
CN403
Expansion valve control
YX2
Relay for High speed (Terminal X2)
YX5
Relay for S-Low speed (Terminal X5)
YX4
Relay for Low speed (Terminal X4)
YX3
Relay for Medium speed (Terminal X5)
R
Terminal board - Fan motor power supply
Switch indication
DSW3
Capacity code
DSW4
Unit model code
DSW5,
RSW2
Refrigerant cycle number setting
DSW6,
RSW1
Indoor unit number setting
DSW7
Fuse recovery and remote control selector