4.5.2 RASC-(8-10)HNPE
PCB1
PCB2
EFR1
TAB3
TAB4
EF1
RY
1
JP1
C7
C8
L2
PCB1 Connector indication
Connector
Name
R1,N1,R2,
S2,T2
Power supply and reverse phase detection
PCN5
Crankcase heater of compressor (oil)
PCN7
Solenoid valve
PCN8
High pressure switch protection, variable
frequency driver alarm, internal thermostat
protection of the motor and float switch.
PCN9
Magnetic contactor for compressor and magnetic
contactor for fan
PCN10
Low pressure switch protection
PCN14
Solenoid valve
PCN100
4-way solenoid valve
PCN406
Power connection between PCB1 and PCB3
THM7
Outdoor air temperature thermistor
THM8
Pipe evaporation temperature thermistor
THM9
Compressor discharge temperature thermistor
CN1
Input function
CN2
Demand input
CN5A
Micro electronic expansion valve
CN6
Transmission between PCB1 and DIP-IPM
CN7
External output
CN8
Transmission from RASC to indoor unit
CN10
Communication line between PCB1 and PCB3
CN100
Discharge pressure (Pd)
CN102
Line connection between PCB1 and PCB3
CN404
Line connection between PCB1 and PCB3
EF1,2,3
EFR1
Power protection
PCB1 Switch indication
Connector
Name
DSW1
Test run
DSW2
Auxiliary function setting
DSW3
Capacity code
DSW4/RSW1
Refrigerant cycle number
DSW5
End terminal resistance
DSW6
Simultaneous / individual operation
PSW1
Forced defrosting
PSW2
Checking mode (
)
PSW3
Checking mode (
)
PCB1 LED indication
LED
Colour
Name
LED1
Red
Power source for the PCB
LED2
Green This LED indicates the transmission status
between the indoor unit and the RCS
LED3
Yellow This LED indicates the transmission status
between the indoor unit and the RASC unit
LED4
Red
Power source at 280V for the PCB
PCB2 Connector indication
Connector
Name
PCN201 Power supply
PCN202
Power connection between PCB3 and PCB1
CN201
Line connection between PCB3 and PCB1
CN202
Line connection between PCB3 and PCB1
EFR1
Power protection
4 Electrical and control settings
Printed circuit board
SMGB0091 rev.2 - 11/2015
65
4