10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
264
Cause of inverter stoppage (
i
)
Code
Cause
Cause of stoppage
for corresponding
unit
Remark
Indication
during retry
Alarm Code
1
Fault signal error of inverter module (DIP-IPM/IPM Error)
(Overcurrent, Undercurrent, Temperature increase, etc.)
17
P7
53
2
Instantaneous overcurrent
17
P7
48
3
Abnormal inverter fin temperature
17
P7
54
4
Electronic thermal activation (Inverter overcurrent)
17
P7
48
5
Voltage decrease (Undervoltage)
18
P8
06
6
Overvoltage
18
P8
06
7
Abnormal inverter transmission
18
-
04
8
Abnormal current detection
17
P7
51
9
Instantaneous power failure detection
18
-
-
11
Reset of micro-computer for inverter
18
-
-
12
Earth fault detection from compressor (Only starting)
17
P7
53
13
Phase detection abnormality
18
-
-
16
Inverter non-operation
18
p8
55
17
Communication abnormality
18
p8
55
18
Protection device activation (PSH)
-
-
02
19
Protection detection device abnormality
-
-
38
20
Early Return Protection Device
18
-
-
21
Synchronism loss detection
17
P7
53
22
PCB setting abnormality
-
-
31
Table of capacity codes of indoor unit
Code
Equivalent horsepower
06
0.8
08
1.0
10
1.3
11
1.5
13
1.8
Code
Equivalent horsepower
14
2.0
16
2.3
18
2.5
22
3.0
32
4.0
Code
Equivalent horsepower
40
5.0
48
6.0
64
8.0
80
10.0