10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
245
10
10.3 Troubleshooting in check mode
10.3.1 Troubleshooting using the remote controller PC-ART
Use the “OK” switch of the remote control in the following cases:
1
When the RUN LED is flickering.
2
To trace back the cause of the malfunction after restarting from the
stoppage while the RUN LED is flickering.
3
To check during the normal operation or during the stoppage.
4
To monitor the inlet air temperature and the discharge air temperature.
Check mode
Check mode 2: The data which was held immediately
before the failure will be displayed
Check mode 1: Current data will be displayed
Normal mode
-
The indication will delay as the transmission between the remote control switch and
the indoor unit takes about ten seconds.
-
All the data may be displayed as "
FF
" or "
1
" or "
255
". These transient data, which
are produced temporarily by the software, do not affect the device functions at all.
(The alarm code may also be displayed as "
FF
".)
Unit number
and alarm code
displayed
The alarm code that identifies the last fault that has occurred
in the displayed unit.
The unit number of the connected unit or the unit number for
which the checking mode was selected previously.
• ADDS: Number of the indoor unit in number ** cycle
• RN: Number ** refrigerant cycle
Check mode 1
(Refer to
for details)
After
seven
seconds
Within seven seconds to check
another unit
Forward:
Press the "
" switch to increase from 00 to 01 to 02 ···
Backward:
Press the "
" switch to decrease from 15 to 14 to 13 ···
Press "
" to see the previous indication
Press "
" to see the next indication
Press "
" to see the next data
Press "
" to see the previous data
Unit number and
alarm code
displayed
Check mode 2
(Refer to
for details)
Check mode
disabled
Press "
"
-
In the check mode 2, the data of the first three units
that are connected serially to a remote control switch
are available.
-
You can press the “OK” switch to disable the check
mode 2. Check mode 1 cannot be disabled even if
you press the “OK” switch.
Press “OK” for
more than 3
seconds
After
seven
seconds
(A)
See (A)
Press “OK” for more than 3 seconds
Press “OK”
for more than
3 seconds