7 Commissioning
Test run procedure from the RASC unit
SMGB0091 rev.2 - 11/2015
127
7
7.5 Test run procedure from the RASC unit
The test run procedure from the RASC unit side is shown below. You can set this DIP switch while the power source is ON.
Setting of dip switch (before shipment)
DSW1
1
Test run
2
Cooling (OFF) / Heating (ON)
3
Intermediate season
4
Manual compressor stop
!
D A N G E R
•
Do not touch any other electrical parts when operating switches on the PCB.
•
Do not attach or detach service cover when the power source for the RASC unit is ON and the RASC unit is operated.
?
N O T E
Turn all DIP switches of DSW1 OFF when the test run operation is completed.
Dip switch setting
Operation
Remarks
Test run
1
Setting operation mode
(a) Cooling:
Set DSW1-1 ON
(b) Heating
SET DSW1-1 and 2 ON
(c) Cooling intermediate season:
Set DSW1-1 and 3 ON
(d) Heating intermediate season:
Set DSW1-1, 2 and 3 ON
•
The indoor unit automatically
starts to operate when the test run
of the RASC unit is set.
•
You can perform the ON/OFF
operation from the remote control
switch or the DSW1-1 of the
RASC unit.
•
Continuous operation during 2
hours is performed without the
Thermo-OFF condition.
?
N O T E
•
TEST RUN operation time can
be increased depressing the time
switch in the Remote Control.
•
If is setting DSW1-3 ON, cooling/
heating intermediate season mode
is activated.
•
Make sure that the indoor units start to
operate in accord with the test run of
the RASC unit.
•
If you start the test run from the RASC
unit and you stop the test run from
the remote control switch, the test
run function of the remote control
switch is cancelled. However, the test
run function of the RASC unit is not
cancelled.
•
If the more than one indoor unit is
connected with one remote control
switch, all the units start the test run at
the same time. Therefore, turn OFF the
power source so that the indoor units
do not perform the test run. If this is the
case, the TEST RUN indication of the
remote control switch may flicker. This
is not abnormal.
•
The setting of DSW1 is not required
for the test run from the remote control
switch.
Manual
OFF of
compressor
2
Forced stoppage of
compressor:
Set DSW1-4 ON
•
When DSW1-4 is ON during
the compressor operation, the
compressor stops operating
immediately and the indoor unit is
under the Thermo-OFF condition.
•
When DSW1-4 is OFF, the
compressor starts to operate after
the cancellation of the 3-minute
guard.
•
Do not turn ON and OFF the
compressor frequently.