Hitachi RAC-35WPB Скачать руководство пользователя страница 1

FOR   SERVICE   PERSONNEL   ONLY

SAFETY PRECAUTION

• Read the safety precautions carefully before operating the unit.

• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

    WARNING .......... Incorrect methods of installation may cause death or serious injury.
    CAUTION .......... Improper installation may result in serious consequence.
    Make sure to connect earth line.

    This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of

the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.

TI

NU 

RO

OD

NI

 WARNING

THE CHOICE OF MOUNTING SITE

 

(Please note the following matters and obtain permission from customer before installation.)

• The unit should be mounted at stable, non-vibratory location

which can provide full support to the unit.

 CAUTION

• No  nearby  heat  source  and  no  obstruction  near  the  air

outlet is allowed.

• The  clearance  distances  from  top,  right  and  left  are

specified in figure below.

• The location must be convenient for water drainage and

pipe connection with the Outdoor unit.

• To avoid interference from noise, please place the unit and

its  remote  controller  at  least  1m  from  the  radio  and
television.

• To avoid any error in signal transmission from the remote

controller,  please  put  the  controller  far  away  from  high-
frequency machines and high-power wireless systems.

TI

NU 

RO

OD

TU

O

 WARNING

• The Outdoor unit must be mounted at a location which can

support heavy weight. Otherwise, noise and vibration will
increase.

 CAUTION

• Do  not  expose  the  unit  under  direct  sunshine  or  rain.

Besides, ventilation must be good and clear of obstruction.

• The air blown out of the unit should not point directly to

animals or plants.

• The clearances of the unit from top, left, right and front are

specified in figure below. At least three of the above sides

must be open air.

• The installation height should be at least 2,300 mm or more

from the floor.

• Be sure that the hot air blown out of the unit and noise do

not disturb the neighbourhood.

• Do not install at a location where there is flammable gas,

steam, oil and smoke.

• The location must be convenient for water drainage.

• Place the Outdoor unit and its connecting cord at least 1 m

away from the antenna or signal line of television, radio or

telephone. This is to avoid noise interference.

Names of Indoor Components

Direction of Piping

Backward piping
from left

Connection

There  are  6  directions  allowed,
namely,  backward  piping,
backward  piping  from  left,
horizontally  piping  from  right,
horizontally  piping  from  left,
vertically down from right, vertically
down from left.

Dimension of Mounting

Stand of the Outdoor unit

(unit : mm)

1

2

Figure showing the Installation
of Indoor and Outdoor Unit.

above
50mm

 above 50mm

 above 50mm

m

m0

03 

tu

ob

a

m54.

0 tu

oba

dn

eb 

to

n t

su

m

The  indoor  piping  should  be
insulated  with  the  enclosed
insulation  pipe.  (If  the  insulator  is
insufficient, please use commercial
products.)

• The refrigerating machine oil is

easily affected by moisture. Use
caution  to  prevent  water  from
entering the cycle.

• The difference in height between

the  indoor  and  outdoor  unit
should be kept below 10m.

• The connecting pipe, no matter

big  or  small,  should  all  be
insulated with insulation pipe and
then  wrapped  with  vinyl  tape.
(The insulator will deteriorate if
it is not wrapped with tape).

The  connection  of  insulated  drain
hose.
          Inner diameter 16mm

Please use insulated drain hose for
the  indoor  piping  (commercial
product)

Be  sure  to
completely
seal any gap
with putty.

TI

N

R

O

O

D

NI

1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe

 CAUTION

• The draining of the water container inside the Indoor unit can be done from the left.

Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.

• Drill  a  ø65mm  hole  on  wall  which  is

slightly tilted towards the outdoor side.
Drill the wall at a small angle.

• Cut the protection pipe according to the

wall thickness.

• Empty gap in the sleeve of protection

pipe should be completely sealed with
putty to avoid dripping of rain water into
the room.

• Please  ensure  smooth  flow  of  water

when installing the drain hose. Improper
installing may wet your funiture.

• An IEC approved power cord should be

used. Power cord type: NYM.

 WARNING

Be sure that the wire is not
in contact with any metal in
the  wall.  Please  use  the
protection  pipe  as  wire
passing through the hollow
part  of  the  wall  so  as  to
prevent  the  possibility  of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and any
dew may drop.

Seal with
putty

Protection
pipe

Sleeve of
protection
pipe

Seal with
putty

Outdoor

Indoor

2-5mm

2 Installation Of The Indoor Unit

WALL

When the power is
supplied from the
indoor unit, pull the
power cable from the
cable drawer at the
right or left side of
the indoor unit.

1

 PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

   Preparation
• Connect connecting cord.
• Pull out the pipe, connecting cord and drain hose.
    Installation
• Insert the pipe through the wall hole.

1

The  upper  part  of  the  Indoor  unit  is  hanged  on  the

hanger.

2

The  projection  at  the  lower  part  of  the  Indoor  unit  is

hooked onto the hanger.

Connecting cords, pipe and

drain hose must be laid

together with Vinyl tape.

2

 PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

   Preparation

Changed of Drain Hose and Installation Procedures.

• Exchange the location of drain hose and drain cap while installing the pipe from the left side as

shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.

• Please use pliers to pull out the drain cap.

(This is an easier way to remove the drain
cap).

 CAUTION

Insufficient  insert  may
result in water leakage.

Drain Hose

Drain cap

• Remove low cover
• Insert drain cap up to the

location securely till the
cap stops.

Cutting Low Cover bush

• While installing the pipe from the right, left or

bottom side, use a knife to cut openings as
shown in figure. Then smoothen the edges of
openings with a file.

Openings

• Push  the  pipe  deeply  until  the  insulating

section of the drain hose end gets over the
rib at the indoor unit side.

Openings

 CAUTION

• The rubber strap used for fixing the insulator

should not be tied with great force. Otherwise,
this will damage heat insulation and causes
water condensation.

• Please pull the lower part of the Indoor unit

outwards to check if the unit is hooked onto
the hanger. Improper installation may cause
vibration and noise.

• Transform the piping while holding down the

lower portion of pipe-support by hand.

Pipe

Rubber strap tied

with great force

INSTALLATION  AFTER CONNECTION OF REFRIGERATING PIPES

• The refrigerating pipe should be adjusted to fit into

the  hole  on  the  wall  and  then  ready  for  further
connection.

• The terminals of 2 connected pipes must be covered

with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.

• Connect  the  connecting  cord  after  removing  low

cover.
(Refer to "CONNECTION OF POWER CORD")

• After adjustment, fit the connecting cord and pipes

into the space available under the unit. Use holder to
hold them tight.

• Holder  can  be  attached  at  the  either  of  2  places.

Please select the easier position.

THE CONNECTION OF REFRIGERATING PIPE DURING

THE INSTALLATION OF INDOOR UNIT

  Preparation To Install Refrigerating Pipes
• The  refrigerating  pipes  and  connecting  cord

transform and are attached.

Please bend at a small
radius to form an arc

   Installation

Hang the indoor unit onto the hanger. Use the temporary stand
at  the  back  of  the  Indoor  unit  to  push  its  lower  part  15cm
forwards.
• Place the drain hose through the hole on the wall.
• Wrap  the  refrigerating  pipes  with  insulation  pipe  after

connecting refrigerating pipe.

• Connect the connecting cord after removing low cover.

(Refer to "Connection of Power Cord")

• After adjustment, the connecting cord and refrigerating pipes

are placed into the space available under the Indoor unit.

• The projection of Indoor unit must hook to the hanger.

Pull this to the front during the
connection of refrigerating
pipe to ease task.

Heat

insulation pipe

Refrigerating

pipe

Connecting

cord

Wall hole

Pipe

Drain hose

Cable

4

Installation of Drain Hose

 CAUTION

Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.

CAUTION

You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Careless may result in water leakage.)

• The connected terminals should be completed sealed

with heat insulator and then tied up with rubber strap.

• Do not tie the terminals with the tape too tight.

If  any  clearance  or  over-tightening  may  cause

condensation.

• Please tie the pipe and power line together with vinyl

tape as shown in the figure showing the installation of

Indoor and Outdoor units.

• To enhance the heat insulation and to prevent water

condensation,  please  cover  the  outdoor  part  of  the

drain hose and pipe with insulation pipe.

• Completely seal any gap with putty.

Insulation material for pipe
connection

Sleeve of
protection pipe

Putty

Putty

Cable drawer (right side)

Wall hole

Drain layout of backward piping from left

The component of 

the package of the outdoor unit.

The end of the refrigerating pipes are at
locations marked with “ ” symbol.

3 Heat Insulation and Finish of the Piping

2,300 mm or more

Drain cap

Pipe

support

Transform after

bending downward.

is included 

in

Insulation pipe (must be wrapped with
vinyl tape at every 120 mm)

5mm

Protection

pipe

Connecting cord

Connected

section

Drain hose

below

Indoor Unit / Outdoor Unit

6&  7

RAC-35WPB

Lift the body
of the unit
upwards and
then force it
downwards.

1

 Hanger

Refrigerating
Pipe

Protection
Pipe

Drain Hose Connecting Cord

Projection

Pipe

Drain hose

Cable

Drain layout of
backward piping

1

 Hanger

pond

Bending upwards Condensed water

Ditch

about 15cm

Hook

Projection

No.

Item

Qty

Hanger

Screw for Hanger

AAA size Battery

Remote Controller

Insulation sheet

Drain Pipe

1

2

3

4

5

6

7

8

9

10

11

Bush

2

2

2

C-case 

 

 

 

Air Cleaning

 

Mesh

 

Wasabi-Nano Titanium 

L.H

Screw for Remote 

Controller Holder

Remote Controller Holder

Plug

10

11

3

4

Direct Mounting On The Wall

Wall Penetration and Installation of Protection Pipe

Please use hidden beams in the wall to hold the hanger.

Procedures of Installation and Precautions

Procedures to fix the hanger.

1.Drill holes on wall.

(As shown below)

2.Push plug into the holes.

(As shown below)

3.Fix the hanger on wall with

4.1 x 32 screw.
(As shown in figure below)

Procedures to fix the holder of remote control.

1.Drill holes on wall.

(As shown below)

2.Push plug into the holes.

(As shown below)

 Remote

Control
Holder

32mm

Wall

ø

m

m8.

4

1

 Hanger

2

 Screw

Wall

Plug (Procure locally)

 

Screw

20mm

ø

m

m4.

4

Wall

Plug
(Procure
locally)

Screw the hanger at the
positions possibly near the
upper and lower hooks where
the indoor unit is hung. Use 4 or
more screws to fix the hanger.

Wall hole

Weight

Line

1

 Hanger

Level

2

 Screw for Hanger

Ceiling

Installation  Of  Remote  Controller

The  remote  controller 

must  be  slide  in

the  remote  controller 

holder,  in  the  direction 

as  shown  in  the  figure, 

until  it  hooks  at  the 

lower  end  of  the  remote 

controller  holder.

Screw  (2  pieces)

Remote 

Controller 

Holder

Remote

Controller

  The  remote  controller  can  be  placed  in  its  holder  which  is 

 fixed  on  wall  or  beam.

  To operate the remote controller at its holder, please ensure 

that the unit can receive signal transmitted from the controller 

at the place where the holder is to be 

when signal is received from the remote controller. The signal 

transmission  is  weaken  by  the fluorescent  light.  Therefore,  

during  the  installation  of  the  remote  control  holder,  please 

switch  on  the  light,  even  during  day  time,  to  determine  the 

mounting  location  of  the  holder.

10

10

11

pond

Condensed water

1

RAK-18_25_35PPA/RAC-18_25_35WPA_IM_English

Maximum pipe length 20m

Minimum pipe length 3m

RAK-50PPB/RAC-50WPB

RAK-35PPB/RAC-35WPB

above 100mm

 above 50mm

give clearance

as wide as

possible

above

200mm

above 200mm

The clearances of the

unit from top, left, right

and front are specified

in figure below. At least

three of the above sides

must be open air.

*

give clearance as wide as possible

 & 

330

310

(10)

10

500

35

50

12

125

Mounting Stand

Mounting
    Stand

12

310

299

500
792

330

RAC-50WPB

above 300mm

For outdoor unit installation, allow at least 

2 sides of space around the unit to ensure 

ventilation flue. 

Drain Hose

550

668

42.5

193

39

37

100

100

115

Visible outline of the

Indoor Unit

180

160

Bush

Bush

(35WPB)

(50WPB)

2

  WARNING

Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the

installation work yourself.

Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause

water leakage, electric shock and fire.

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may

collapse and impose danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing

with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and

fire may occur due to the use of low quality wire or improper work.

Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the

conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the

terminal base. Improper insertion and loose contact may cause over-heating and fire.

Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or

stronger vibration may occur.

Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)

does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally

which could result in a rupture and injury.

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may

occur.

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the

room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner

technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.

Be sure to connect the earth line from the power supply wire to the outdoor unit and between

the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the

telephone unit. Improper earthing may cause electric shocks.

When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.

If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a

pressure in the freezing cycle system will build up steeply, causing an explosion or injury.

When installing the unit, be sure to install the refrigerant pipe before starting the compressor.

If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the

pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

  CAUTION

A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the

outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.

Without a circuit breaker, the danger of electric shock exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire

if flammable gas leaks around it.

Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.

An IEC approved power cord should be used. Power cord type: NYM.

The electric cables should neither be reworked nor  added.

Make sure to use an exclusive circuit breaker.

Otherwise fire or electric shock might occur by connection failure, isolation failure or over current. 

Make sure to connect cables to terminal properly and terminal cover should close firmly. 

Otherwise,  over heating at terminal contact, fire or electric shock might occur.
Make sure that there is no dust on  any connected points of electric cables and fix firmly.

Otherwise, fire or electric shock might occur. 

2

Pipe

Connecting
cord

Drain hose

EN

Отзывы: