RAS-25YHA1/RAC-25YHA1_EN.p65

  

FOR  SERVICE  PERSONNEL  ONLY

Carefully read through the procedures of proper 

installation before starting installation work.

The sales agent should inform customers regarding 

the correct operation of installation.

(Mark          is exclusive use tool for R410A)                

Screwdriver    •    Measuring Tape    •    Knife    •    Saw

•   ø65mm  Power  Drill    •    Hexagonal  Wrench  Key 

(     4mm) • Wrench (14,17,19,22mm)     Gas leakage

Detector • Pipe Cutter • Putty • Vinyl Tape • Pliers  • 

Flare Tool                Vacuum Pump Adapter              Manifold Valve

   Charge Hose    Vacuum Pump

Tools Needed For Installation Work

SAFETY PRECAUTION

• Read the safety precautions carefully before operating the unit.

• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING .......... Incorrect methods of installation may cause death or serious injury.

CAUTION .......... Improper installation may result in serious consequence.

Make sure to connect earth line.

This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of

the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.

WARNING

Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the

installation work yourself.

Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause

water leakage, electric shock and fire.

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may

collapse and impose danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing

with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and

fire may occur due to the use of low quality wire or improper work.

Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the

conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the

terminal base. Improper insertion and loose contact may cause over-heating and fire.

Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or

stronger vibration may occur.

Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)

does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally

which could result in a rupture and injury.

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may

occur.

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the

room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner

technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.

Be sure to connect the earth line from the power supply wire to the outdoor unit and between

the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the

telephone unit. Improper earthing may cause electric shocks.

When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.

If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a

pressure in the freezing cycle system will build up steeply, causing an explosion or injury.

When installing the unit, be sure to install the refrigerant pipe before starting the compressor.

If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the

pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the

outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.

Without a circuit breaker, the danger of electric shock exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire

if flammable gas leaks around it.

Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.

An IEC approved power cord should be used. Power cord type: NYM.

INDOOR UNIT

 WARNING

THE CHOICE OF MOUNTING SITE

 (Please note the following matters and obtain permission from customer before installation.)

The unit should be mounted at stable, non-vibratory location 

which can provide full support to the unit.

 CAUTION

OUTDOOR UNIT

 WARNING

 CAUTION

Names of Indoor Components

No.

Item

Qty

Hanger

Screw for Hanger

Holder for Remote 

Controller

AAA size Battery

Screw for holder of 

Remote Controller

Remote Controller

Insulation sheet

Drain Pipe

(4.1 x 32)

(3.1 x 16)

1

2

3

4

5

6

7

8

9

0

1

6

1

2

2

1

1

1

1

Direction of Piping

Connection

(unit : mm)

Figure showing the Installation 

of Indoor and Outdoor Unit.

INDOOR UNIT

1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe

 CAUTION

Direct Mounting On The Wall

• Please use hidden beams in the wall to hold the hanger.

Procedures of Installation and Precautions

• Procedures to fix the hanger.

.

2

.

1

3.

• Procedures to fix the holder of remote control.

.

2

.

1

Wall Penetration and Installation of Protection Pipe

 WARNING

2 Installation Of The Indoor Unit

Holder

 PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

   Preparation


    Installation
• Insert the pipe through the wall hole.

1

2

 PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

Preparation

Changed of Drain Hose and Installation Procedures

 CAUTION

Cutting Low Cover bush

 CAUTION

INSTALLATION  AFTER CONNECTION OF REFRIGERATING PIPES

THE CONNECTION OF REFRIGERATING PIPE DURING 

THE INSTALLATION OF INDOOR UNIT

Preparation To Install Refrigerating Pipes

below

5mm

Please bend at a small

radius to form an arc

Installation

4 Installation of Drain Hose

 CAUTION

CAUTION

Cable drawer (right side)

3 Heat Insulation and Finish of the Piping

1

The components of 9  is included in the 

package of the outdoor unit.

No  nearby  heat  source  and  no  obstruction  near  the  air 

outlet is allowed.

The  clearance  distances  from  top,  right  and  left  are 

specified in figure below.

The location must be convenient for water drainage and 

pipe connection with the Outdoor unit.

To  avoid  interference  from  noise,  please  place  the  unit 

and its remote controller at least 1m from the radio and 

television.

To avoid any error in signal transmission from the remote 

controller,  please  put  the  controller  far  away  from  high-

frequency machines and high-power wireless systems.

The Outdoor unit must be mounted at a location which can 

support heavy weight. Otherwise, noise and vibration will 

increase.

Do  not  expose  the  unit  under  direct  sunshine  or  rain. 

Besides, ventilation must be good and clear of obstruction.

The air blown out of the unit should not point directly to 

animals or plants.

The clearances of the unit from top, left, right and front are 

specified  in  figure  below.  At  least  two  of  the  above 

sides must be open air.

The installation height should be at least 2,300 mm or more 

from the floor.

Be sure that the hot air blown out of the unit and noise do 

not disturb the neighbourhood.

Do not install at a location where there is flammable gas, 

steam, oil and smoke.

The location must be convenient for water drainage.

Place the Outdoor unit and its connecting cord at least 1 m 

away from the antenna or signal line of television, radio or 

telephone. This is to avoid noise interference.

When the power is 

supplied from the 

indoor unit, pull the 

power cable from the 

cable drawer at the 

right or left side of 

the indoor unit. 

Backward piping 

from left

There  are  6  directions  allowed, 

namely,  backward  piping, 

backward  piping  from  left, 

horizontally  piping  from  right, 

horizontally  piping  from  left, 

vertically down from right, vertically 

down from left.

Dimension of Mounting 

Stand of the Outdoor unit

The refrigerating pipe should be adjusted to fit into 

the  hole  on  the  wall  and  then  ready  for  further 

connection.

The terminals of 2 connected pipes must be covered 

with insulator used for terminal connection. Then the 

pipes are wrapped with insulation pipe.

Connect  the  connecting  cord  after  removing  low 

cover.

(Refer to "CONNECTION OF POWER CORD")

After adjustment, fit the connecting cord and pipes 

into the space available under the unit. Use holder to 

hold them tight.

Holder  can  be  attached  at  the  either  of  2  places. 

Please select the easier position.

The  refrigerating  pipes  and  connecting  cord 

transform and are attached.

While installing the pipe from the right, left or 

bottom side, use a knife to cut openings as 

shown in figure. Then smoothen the edges of 

openings with a file.

Connect connecting cord.

Pull out the pipe, connecting cord and drain hose.

The  upper  part  of  the  Indoor  unit  is  hanged  on  the 

hanger.

The projection at the lower part of the Indoor unit is 

hooked onto the hanger.

Hang the indoor unit onto the hanger. Use the temporary stand 

at  the  back  of  the  Indoor  unit  to  push  its  lower  part  15cm 

forwards.

Place the drain hose through the hole on the wall.

Wrap  the  refrigerating  pipes  with  insulation  pipe  after 

connecting refrigerating pipe.

Connect the connecting cord after removing low cover. 

(Refer to "Connection of Power Cord")

After adjustment, the connecting cord and refrigerating pipes 

are placed into the space available under the Indoor unit.

The projection of Indoor unit must hook to the hanger.

The connected terminals should be completed sealed 

with heat insulator and then tied up with rubber strap.

Do not tie the terminals with the tape too tight.

If  any  clearance  or  over-tightening  may  cause 

condensation.

Please tie the pipe and power line together with vinyl 

tape as shown in the figure showing the installation of 

Indoor and Outdoor units.

To  enhance  the  heat  insulation  and  to  prevent  water 

condensation,  please  cover  the  outdoor  part  of  the 

drain hose and pipe with insulation pipe.

Completely seal any gap with putty.

Be sure that the drain hose is 

not loosely connected bend or 

proper condition like left figure.

You are free to choose the side (left or right) for the installation of drain 

hose. Please ensure the smooth flow of condensed water of the Indoor 

unit during installation. (Careless may result in water leakage.)

The rubber strap used for fixing the insulator 

should not be tied with great force. Otherwise, 

this will damage heat insulation and causes 

water condensation.

Please pull the lower part of the Indoor unit 

outwards to check if the unit is hooked onto 

the hanger. Improper installation may cause 

vibration and noise.

Transform the piping while holding down the 

lower portion of pipe-support by hand.

Be sure that the wire is not 

in contact with any metal in 

the  wall.  Please  use  the 

protection  pipe  as  wire 

passing through the hollow 

part  of  the  wall  so  as  to 

prevent  the  possibility  of 

damaged by mouse. 

Unless it seals completely 

any air with high humidity 

flows from outdoor and any 

dew may drop.

Remove low cover

Insert drain cap up to the 

location  securely  till  the 

cap stops.

Insufficient  insert  may 

result in water leakage.

Exchange the location of drain hose and drain cap while installing the pipe from the left side as 

shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.

Please use pliers to pull out the drain cap. 

(This is an easier way to remove the drain 

cap).

Push  the  pipe  deeply  until  the  insulating 

section  of  the  drain  hose  end  gets  over 

the rib at the indoor unit side.

Drain layout of 

backward piping

Drill  a  ø65mm  hole  on  wall  which  is 

slightly tilted towards the outdoor side. 

Drill the wall at a small angle.

Cut the protection pipe according to the 

wall thickness.

Empty gap in the sleeve of protection 

pipe should be completely sealed with 

putty to avoid dripping of rain water into 

the room.

Please  ensure  smooth  flow  of  water 

when installing the drain hose. Improper 

installing may wet your funiture.

An IEC approved power cord should be 

used. Power cord type: NYM.

Fix the hanger on wall with 

4.1 x 32 screw

(As shown in figure below)

Push plug into the holes. 

(As shown below)

Push plug into the holes. 

(As shown below)

Drill holes on wall.

(As shown below)

Drill holes on wall.

(As shown below)

Screw the hanger at the 

positions possibly near the 

upper and lower hooks where 

the indoor unit is hung. Use 4 or 

more screws to fix the hanger.

The draining of the water container inside the Indoor unit can be done from the left. 

Therefore the hanger must be fixed horizontally or slightly tilted towards the side of 

drain hose. Otherwise, condensed water may overflow the water container.

HITACHI SPLIT-UNIT AIR CONDITIONER 

INSTALLATION MANUAL

  CAUTION

1

Indoor Unit / Outdoor Unit

RAS-25YHA2 / RAC-25YHA2

3 Remote 

Control

Holder

 Plug

5  Screw

Wall hole

Pipe

Drain hose

Cable

Wall hole

Weight

Line

Hanger

Level

2  Screw for Hanger

450mm

400mm

316mm

125mm

41mm

45mm

ø65mm

199mm

280mm

65mm

390mm

80mm

530mm

780mm

10mm

45mm

ø65mm

42mm

44mm

125mm

20mm

Drain Hose

Drain Hose

Visible outline of the 

indoor unit

Wall hole

32mm

Wall

ø4.8m

m

1  Hanger

2  Screw

Wall

above 50mm

4.1 x 32 screw

Ceiling

20mm

ø4.4mm

Wall

Seal with

putty

Protection

pipe

Sleeve of

protection

pipe

Seal with

putty

Outdoor

Indoor

2-5mm

WALL

Pipe

Rubber strap tied 

with great force

Drain Hose

Drain cap

Rib at the Indoor unit

Insulation material for pipe 

connection

Sleeve of 

protection pipe

Putty

Putty

The end of the refrigerating pipes are at 

locations marked with “    ” symbol.

0.85m

Insulating 

section of the 

drain hose end

(Procure locally)

(Procure locally)

Plug

Purifying Filter

Mounting Stand

(9)

9

300

500

100

12

30

45

282

Openings

Openings

Connecting cords, pipe and

drain hose must be laid

together with Vinyl tape.

Lift the body

of the unit

upwards and

then force it

downwards.

1  Hanger

Refrigerating

Pipe

Protection

Pipe

Drain Hose Connecting Cord

1  Hanger

Projection

1

2

Drain cap

Pipe

support

Transform after

bending downward.

Holder

Pipe

Connecting

cord

Drain hose

Insulation pipe (must be wrapped with

vinyl tape at every 120 mm)

about 15cm

Hook

Projection

Protection

pipe

Pull this to the front during the

connection of refrigerating

pipe to ease task.

Heat

insulation pipe

Connecting cord

Holder

Connected

section

Refrigerating

pipe

Connecting

cord

Drain hose

Wall hole

Pipe

Drain hose

Cable

Drain layout of backward piping from left

Condensed

water pond

Bending upwards Condensed water

pond

Ditch

1

2

6

7

4

5

3

above

50mm

 above 50mm

 above 50mm

m

m0

03 

tu

ob

a

m54.

0 tu

oba

dn

eb 

to

n t

su

m

Used in

horizontal piping

The  indoor  piping  should  be

insulated  with  the  enclosed

insulation pipe. (If the insulator is

insufficient, please use commercial

products.)

• The refrigerating machine oil is

easily affected by moisture. Use

caution  to  prevent  water  from

entering the cycle.

• The difference in height between

the  indoor  and  outdoor  unit

should be kept below 10m.

• The connecting pipe, no matter

big  or  small,  should  all  be

insulated with insulation pipe and

then  wrapped  with  vinyl  tape.

(The insulator will deteriorate if

it is not wrapped with tape).

The connection of insulated drain

hose.

          Inner diameter 16mm

Please use insulated drain hose for

the  indoor  piping  (commercial

product)

above 100mm

 above 400mm

 above 150mm

give clearance

as wide as

possible

above

200mm

Be  sure  to

completely

seal any gap

with putty.

m0

2 ht

gn

el 

epi

mu

mix

a

M

above 200mm

Plug (Procure locally)

2,300 mm or more

The clearances of the

unit from top, left, right

and front are specified

in figure below. At least

three of the above sides

must be open air.