Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–42
Alarm Signal
The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.
We must make a distinction between the alarm
signal AL and the alarm relay contacts [AL0],
[AL1] and [AL2]. The signal AL is a logic
function, which you can assign to the open collec-
tor output terminals [11] or [12] or the relay
outputs. The most common (and default) use of the relay is for AL, thus the labeling of
its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic
signal interface or to energize a small relay (50 mA maximum). Use the relay output to
interface to higher voltage and current devices (10 mA minimum).
Run
Stop
Trip
Fault
Fault
Alarm signal active
STOP
RESET
STOP
RESET
RUN
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
05
AL
Alarm Signal
ON
when an alarm signal has occurred and has not
been cleared
OFF
when no alarm has occurred since the last
clearing of alarm(s)
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
C026, C036
Notes:
•
By default, the relay is configured as normally
closed (C036=01). Refer to the next page for an
explanation.
•
In the default relay configuration, an inverter power
loss turns ON the alarm output. the alarm signal
remains ON as long as the external control circuit
has power.
•
When the relay output is set to normally closed, a
time delay of less than 2 seconds occurs after
powerup before the contact is closed.
•
Terminals [11] and [12] are open collector outputs,
so the electric specifications of [AL] are different
from the contact output terminals [AL0], [AL1],
[AL2].
•
This signal output has the delay time (300 ms
nominal) from the fault alarm output.
•
The relay contact specifications are in
Logic Signal Specifications” on page 4–6
contact diagrams for different conditions are on the
next page.
RY
+
–
Example for terminals [AL0], [AL1], [AL2]
(default output configuration shown—
see page
Relay position
shown is for
normal opera-
tion (no alarm).
Example for terminal [11] or [12] (requires
output configuration—see page
AL0
AL2
AL1
Inverter logic
circuit board
Inverter output
terminal circuit
See I/O specs
on page
AL
AL
Load
Power
supply
12 11
CM2
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...