L100 Inverter
Oper
ations
and Monitor
ing
4–27
Alarm Signal
The inverter alarm signal is active
when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.
We must make a distinction between the alarm
signal
AL and the alarm relay
contacts
[AL0],
[AL1] and [AL2]. The signal AL is a logic
function, which you can assign to the open collec-
tor output terminals [11] or [12]. The relay is
dedicated to the function AL, thus the labeling of its terminals. Use an open collector
output (terminal [11] or [12]) for a low-current logic signal interface or to energize a
small relay (50 mA maximum). Use the relay output to interface to higher voltage and
current devices (10 mA minimum).
RUN
STOP
RESET
STOP
RESET
Run
Stop
Trip
Fault
Fault
Alarm signal active
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
05
AL
Alarm Signal
ON
when an alarm signal has occurred and has not
been cleared
OFF
when no alarm has occurred since the last
clearing of alarm(s)
Valid for outputs:
11, 12
Required settings:
C_33
Notes:
•
When the alarm output is set to normally closed, a
time delay of less than 2 seconds occurs until the
contact is closed when the power is turned ON.
•
Terminals 11 and 12 are open collector outputs, so
the electric specifications of [AL] are different
from the contact output terminals [AL0], [AL1],
[AL2].
•
When the inverter power supply is turned OFF, the
alarm signal output is valid as long as the external
control circuit has power.
•
This signal output has the delay time (300 ms
nominal) from the fault alarm output.
•
The relay contact specifications are in
tions of Control and Logic Connections” on
page 4–6
. The contact diagrams for different condi-
tions are on the next page.
Example for terminal [11] or [12] (requires
output configuration—see page
):
RY
+
–
Example for terminals [AL0], [AL1], [AL2]
(default output configuration shown—
see page
):
See I/O specs
on page
12 11
L
H O OI
FM CM2
Inverter logic
circuit board
Relay position
shown is during
normal running
(no alarm).
AL0
AL2
AL1
AL
Inverter output
terminal circuit
AL
Load
Power
supply
Содержание L100 Series
Страница 145: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 168: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 176: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 183: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 186: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 L100 inverter with footprint type filter ...
Страница 187: ...L100 Inverter Appendix C C 5 L1 L2 L3 PE L100 inverter with book type filter M 3 ...