29
HX-RIO3 Series
6.6. Serial Communication Settings
Setting according to the each communication state is possible because RIO3-CP3MBT is available for
RS232 and RS485 serial communication.
•
Station Setting
The following illustration is an area of Register 0x160A address that can be used to set the code of Serial
communication. High 1byte is the area of rs232, and Low 1byte is the area of rs485.
It is possible to set a maximum of 247 for each area. (default : 1)
MSB LSB
0x160A
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
RS232C Modbus station RS485 Modbus station
•
RS232/ RS485 Communication setting
The options for the communication can be selected.
RS232 can be selected from the
register address, “0x1606”.
RS485 can be selected from the register address, “0x1608”.
- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve
MSB LSB
0x1607
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Data bit Stop bit Parity bit Reserve
RS232
MSB LSB
0x1609
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Data bit Stop bit Parity bit Reserve
RS485
•
Baud rate setting
The baud rate from 2400bps to 115200bps is supported.
RS232 can be
selected from the register address, “0x1606”.
RS485 can be selected from the register
address, “0x1608”.
0 : 115200(Default) 1 : 2400 2 : 4800 3 : 9600
4 : 19200 5 : 38400 6 : 57600 7 : 115200
Содержание HX-RIO3 Series
Страница 1: ...1 HX RIO3 Series Version 1 02 MODBUS Programmable I O RIO3 CP3MBT User Manual ...
Страница 2: ...2 HX RIO3 Series DOCUMENT CHANGE SUMMARY REV PAGE REMARKS DATE EDITOR 1 02 All new Jan 21 Faber ...
Страница 36: ...36 HX RIO3 Series 4 Search the file to download using a search button 5 Click a Upload Button ...
Страница 37: ...37 HX RIO3 Series 6 If it finish you can see a below message File Upload Done And click a Reset Adapter button ...