8.5 Troubleshooting by using the 7-segment display
Only the authorized person can carry out checks using this method. The operating conditions and each part of the refrigerant
cycle can be checked with the 7-segment display and pushswitches on the PCB1 in the outdoor unit.
(1) Before carrying out checks
(a) Turn ON the main power supply switch. Wait more than 20 seconds before starting the checks.
(b) Check items:
•
Connection information.
•
Information of the outdoor unit.
•
Information of the indoor unit.
•
Information of the cause of the alarm code.
•
Alarm code historical information.
(c) Check the location of the 7-segment display and the pushswitches.
D A N G E R
The PCB and the electrical components are powered by AC 220-240 V. Never touch the electrical parts and the
cables when carrying out the checks.
(2) Location of the pushswitches and the 7-segment display
The pushswitches and the 7-segment display are located on PCB1.
PCB1
211
20CHG
52C1
Fan
SEG1
CH2
20F2
20A2
52C2
CH1
20A1
20B
20C
20F1
X2
X1
212
SEG2
PSW5
PSW1
PSW4
PSW2
PSW3
7-Segment
Display
(3) Protection control code on the 7-segment display
•
A protection control code is displayed on the 7-segment display during the operation when the protection control has
been activated.
•
A protection control code is displayed while the function is operating, and it is cancelled when it is released.
•
When several protection controls are activated, the code number with the highest priority is displayed (see below for
the order of priority).
(a) Higher priority will be given to the protection control related with the frequency control.
<1> Pressure ratio control
<6> Low pressure decrease protection
<2> High pressure increase protection
<7> Demand current control (running current limit control)
<3> Current protection
<8> Low pressure increase protection
<4> Inverter fin temperature increase protection
<9> High pressure decrease protection
<5> Discharge gas temperature increase protection
8 Troubleshooting
245
SMGB0065 rev. 1 - 12/2010