1
TROUBLESHOOTING
79
n
Dip Switches and LED Functions on Outdoor Unit Printed Circuit Boards
Name of Internal
Circuit Board
Part Name
Contents of Functions
®
DSW1
Setting of Outdoor Unit Number
¯
DSW2
Setting of Capacity Code
Outdoor unit capacity is set according to nominal capacity (HP).
°
DSW3
Setting of Height Difference
The height difference between outdoor and indoor units is set.
±
DSW4
A. Test Running for Cooling or Heating
An outdoor unit can be run for testing. When testing has been finished, reset the
function.
B. Forced Stoppage of Compressor
When performing test running or inspection, compressors can be forcedly
stopped to ensure safety.
²
DSW5
(Optional
Function)
A. Changeover of Defrosting Condition
The defrosting operation for normal areas or cold areas can be changed over.
B. Power Supply Changeover Switch #7 pin 380V: OFF, 415V: ON
³
DSW6
Setting of Piping Length
The total piping length between the outdoor unit and indoor unit is set.
´
DSW7
Setting of Emergency Operation
µ
DSW8
Test Operation and Service Setting II
No setting is required.
¶
DSW9
Optional Function 2
·
DSW10
Transmitting Setting
¸
PSW1
Manual Defrosting Switch
The defrosting operation is manually available under the forced defrosting area.
¹
PSW2
º
PSW3
Check Switches
When checking units, checking items can be selected by these switches.
»
LED1
(Red)
Power Source for PCB1
Normal Condition: Activated
Abnormal Condition: Deactivated
¼
LED2
(Green)
This LED2 indicates the transmission state between the PCB1 and PCB3
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
½
LED3
(Yellow)
This LED3 indicates the transmission state between the indoor unit and outdoor
unit.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
Controlling Board:
PCB1
¾
SGE1
SGE2
These indicate the following: ”alarm”, ”protective safety device has tripped” or
”checking items”.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...