1
TROUBLESHOOTING
75
n
ACTIVATING CONDITION OF PROTECTION CONTROL CODE
For following the conditions as the temperature change,
etc., the control of frequency, etc. is performed to prevent
the abnormal conditions by the protection control.
The activating conditions of protection control are shown in
the table below
Code
Protection Control
Activating Condition
Remarks
P01
Pressure Ratio
Control
Compression Ratio
9
Frequency Decrease
(Pd/(Ps+1.3))
2.2
Frequency Increase
Ps: Suction Pressure of
Compressor
P02
High-Pressure
Rise Protection
Pd
2.35MPa (23.5kgf/cm
2
G)
Frequency Decrease
Pd: Discharge Pressure of
Compressor
P03
Current Protection
Inverter Output Current
14A
Frequency Decrease
-
P05
Discharge Gas
Temperature Rise
Protection
Temperature at the top of compressor is high
Frequency Increase (Maximum temperature is
different depending on the frequency.)
-
P06
Low-Pressure Fall
Protection
Low-Pressure Is Excessively Low
Frequency Increase (Minimum pressure is
different depending on the ambient temperature.)
-
P07
4-Way Valve
Switching Control
(For 16, 20HP)
When Switching,
D
P<0.5MPa (5kgf/cm
2
G)
Frequency Increase
D
P<1.3MPa (13kgf/cm
2
G)
Frequency Decrease
D
P=Pd-Ps
P08
Oil Return Control
Frequency less than 40Hz is maintained for more than
1 hour
Frequency
40Hz
-
P09
High-Pressure Fall
Protection
Pd
0.69MPa (7.0kgf/cm
2
G)
Frequency Increase (When Cooling Operation)
Pd
1.52MPa (15.5kgf/cm
2
G)
Frequency Increase (When Heating Operation)
Pd: Discharge Pressure of
Compressor
P11
Pressure Ratio
Falling Retry
Compression Ratio (Pd/(Ps+1.3)<1.8)
When activating 3 times
in an hour, “43” alarm is
indicated.
P12
Low-Pressure
Rising Retry
Ps>0.9MPa (9kgf/cm
2
G)
When activating 3 times
in an hour, “44” alarm is
indicated.
P13
High-Pressure
Rising Retry
Ps>2.7MPa (27kgf/cm
2
G)
(In case of 20 ~ 30Hz: Pd>2.5MPa (25kgf/cm
2
G))
When activating 3 times
in an hour, “45” alarm is
indicated.
P14
Overcurrent Retry of
Constant Compressor
Current
Maximum Value(
v
1),
or Current<0.9A
When activating 3 times
in an hour, “39” alarm is
indicated.
P15
Vacuum/Discharge
Gas Temperature
Rising Retry
In Case of
Ps>0.02MPa (0.2kgf/cm
2
G) over 12 minutes,
Discharge Gas Temperature
132°C over 10 minutes
or Discharge Gas Temperature
140 °C over
5 seconds
When activating 3 times in 30
minutes, “47”(Ps) or “08”
(Discharge Gas) alarm is
indicated.
P16
Discharge Gas
SUPERHEAT
Falling Retry
Discharge Gas SUPERHEAT less than 10 deg. is
maintained for an hour.
When activating 2 times
in 2 hours, “07” alarm is
indicated.
P17
Inverter Trip Retry
Automatic Stoppage of Transistor Module,
Activation of Electronic Thermal
or Abnormal Current Sensor
When activating 3 times
in 30 minutes, “51”, “52” and
“53” alarm is indicated.
P18
Voltage Falling /
Excessive Voltage
Retry
Insufficient/Excessive Voltage at Inverter Circuit
or CB Condenser Part
When activating 3 times
in 30 minutes, “06” alarm is
indicated.
Note: The maximum value (
v
1) is as follows:
Model
380-415V, 50 Hz
8 HP
12.1 A
10 HP
15.0 A
16 HP
17.8 A
20 HP
17.8 A
1. During protection control (except during alarm
stoppage), the protection control code is indicated.
2. The protection control code is indicated during
protection control and turns off when canceling the
protection control.
3. After retry control, the condition of monitoring is
continued for 30 minutes.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...